background image

Output Calibration

Input and output ranges, if specified on your order, are factory 
pre-configured (at 24°C ±1°C). 
Front-mounted Zero and Span potentiometers are used to 
calibrate the output to compensate for load and lead variations.
Note: Perform the following calibration procedure any time 
switch settings are changed.
1.  Apply power to the module and allow a minimum 20 minute 

warm up time.

2.  Using an accurate frequency calibration source such as a 

signal generator, provide an input to the module equal to 
the minimum input required for the application.

  In the most cases the minimum input signal will be 0 Hz.
3.  Set the frequency calibration source equal to the maximum 

input required for the application. This will typically be 
within 10% of the range selected with switches A and B.

4.  Adjust the Span pot for the exact maximum output desired. 

The Span control should only be adjusted when the input 
signal is at its maximum. This will produce the correspond-
ing maximum output signal. 

  For example: 4 mA for a 4-20 mA output or –10 V for a 

±10V output.

5.  Repeat adjustments for maximum accuracy.

Sensitivity Adjustment 

This multi-turn potentiometer provides an adjustable threshold 
level that the incoming signal must overcome before an output 
can be produced. 
This is used to limit noise and minimize false input signals that 
may cause erroneous readings.
When fully clockwise (maximum sensitivity), the input thresh-
old is typically ±25 mV. 
In the fully counterclockwise position (minimum sensitivity), the 
input threshold is typically ±2.5 volts.

Output Test Function

When the Test button is depressed it will drive the output with a 
known good signal that can be used as a diagnostic aid during 
initial start-up or troubleshooting. When released, the output 
will return to normal.
The Test Cal. potentiometer is factory set to approximately 
50% output. It can be adjusted to set the test output from 0 to 
100% of the output span. Press and hold the Test button and 
adjust the Test Cal. potentiometer for the desired output level.

Operation

The APD 7580 accepts a frequency input and provides an 
optically isolated DC voltage or current output that is linearly 
related to the input. 
The frequency input to the APD 7580 is capacitively coupled 
(to remove any DC component at the input) to a comparator 
whose threshold is determined by the setting of the sensitivity 
control. The output from the comparator passes through an 
opto-coupler to the output stage.
The green LoopTracker

®

 input LED provides a visual indica-

tion that a signal is being sensed by the input circuitry of the 
module. The LED illuminates when the input is sufficiently 
large to trigger the input comparator depending on the input 
sensitivity adjustment. 
It also indicates the input signal range by changing in intensity 
as the frequency changes from minimum to maximum. If the 
LED fails to illuminate, or change in intensity as the frequency 
changes, it may indicate a problem with module power, or 
signal input wiring.
Note that it may be difficult to see the LEDs under bright light-
ing conditions.
The red LoopTracker output LED provides a visual indication 
that the output signal is functioning. It becomes brighter as 
the input and the corresponding output change from minimum 
to maximum. 
For current outputs, the red LED will only light if the output loop 
current path is complete. For either current or voltage outputs, 
failure to illuminate or a failure to change in intensity as the 
process changes may indicate a problem with the module 
power or signal output wiring. 

Calibration, Output Test, Operation 

APD 7580

Test Cal.

Span

Zero

Test

Input

Output

Sensitivity

Loop
Tracker

Loop
Tracker

APD 7580

Frequency to DC

Isolated Transmitter

Output Test Level 

Adjustment

Push to Test 

Output

Output Span 

Calibration

Output Zero 

Calibration

Variable 

Brightness Output 

Indicator

Variable 

Brightness Input 

Indicator

Input Sensitivity 

Adjustment

api-usa.com

1220 American Way Libertyville, IL 60048 
Phone: 

800-942-0315

 

Fax: 800-949-7502

A

A

BSOLUTE

BSOLUTE

 P

 P

ROCESS

ROCESS

 I

 I

NSTRUMENTS

NSTRUMENTS

Summary of Contents for APD 7580

Page 1: ...n saving time during initial startup and or troubleshooting All models are field rangeable For APD 7580 specify if UL version is required Order options and accessories as required Order D versions for operation on low voltage power How to Order Free factory setup Please specify on your order Input range Output range Frequency Input Ranges 0 100 Hz to 0 30 kHz 30 switch selectable input ranges Mini...

Page 2: ...H980V H981V H982V H962V H983V H985V H965V H986V H9B6V H9B8V H980I H981I H982I H962I H983I H985I H965I H986I 0 20 kHz HA80V HA81V HA82V HA62V HA83V HA85V HA65V HA86V HAB6V HAB8V HA80I HA81I HA82I HA62I HA83I HA85I HA65I HA86I 0 22 kHz HB80V HB81V HB82V HB62V HB83V HB85V HB65V HB86V HBB6V HBB8V HB80I HB81I HB82I HB62I HB83I HB85I HB65I HB86I 0 24 kHz HC80V HC81V HC82V HC62V HC83V HC85V HC65V HC86V H...

Page 3: ...ut is unpowered or passive APD module provides the loop power 10 9 20 V switch E set to I Measuring recording device accepts a mA current input and provides power to the current loop 11 10 switch E set to I Spring Clip Upper Mount Lower Mount Mounting to a DIN Rail Install module vertically on a 35 mm DIN rail in a protective enclosure away from heat sources Do not block air flow Allow 1 25 mm abo...

Page 4: ...ss and hold the Test button and adjust the Test Cal potentiometer for the desired output level Operation The APD 7580 accepts a frequency input and provides an optically isolated DC voltage or current output that is linearly related to the input The frequency input to the APD 7580 is capacitively coupled to remove any DC component at the input to a comparator whose threshold is determined by the s...

Reviews: