background image

Potentiometer Input to DC Transmitters, Isolated, Field Rangeable 

APD 4008

Input:

 100 

 to 1 M

 Potentiometers, 0 to 90% Offset

Output:

 

0-1 V to ±10 VDC, or 0-2 mA to 20 mADC

 

O

One Minute Setup for Hundreds of I/O Ranges

 

O

External Switches & Table for Range Selection

 

O

Removable Plugs for Faster Installation

 

O

Full 1200 V Input/Output/Power Isolation

 

O

Input and Output LoopTracker

®

 LEDs

 

O

Functional Output Test Button

 

O

Selectable Sink/Source for Current Output

 

Q

Over, Under, Out-of-Range Position Monitoring

 

Q

Remote Control of Positioning Devices

 

Q

Simplify Control of Potentiometer Outputs

Applications

Options–add to end of model number
DF

 

Fast response time, consult factory. DF option will 
cause output noise levels to be greater than  
standard specifications. 

U

 

Conformal coating for moisture resistance

Accessory—order as separate line item
API BP4

  Spare 4-terminal plug, black

All models are field rangeable 

Models can be pre-set to your specifications. 
Order APD 4008 D for operation on low voltage power.

Model

Input

Output

Power

APD 4008

Field configurable—specify range if 

factory is to set switches

Field configurable—specify range if 

factory is to set switches

85-265 VAC, 50/60 Hz or 

60-300 VDC

APD 4008 D

9-30 VDC or 10-32 VAC

Description

The APD 4008 accepts a resistance input from potentiometer, 
slidewire, linear position, displacement, or rotational devices 
and provides an optically isolated DC voltage or current output 
that is linearly related to the potentiometer position.
The APD 4008 will accept any potentiometer with a value of 
0-100 

 through 0-1 M

 without recalibration and without

affecting accuracy. The APD 4008 output can be field-con-
figured via external rotary and slide switches. Offsets and/or
input ranges other than 0 to 100% of the potentiometer range
can also be selected.
The full 3-way (input, output, power) isolation makes this mod-
ule useful for ground loop elimination, common mode signal 
rejection or noise pickup reduction.

Sink/Source Output

The APD 4008 has a 20 VDC loop excitation supply for the 
output. This power supply can be used to power a passive mA 

device. If not required, the APD 4008 output can be wired as 
a passive output. Sinking/sourcing versatility allows the APD 
4008 to produce a powered or unpowered mA output allowing 
it to work with powered or unpowered mA devices.

LoopTracker 

API exclusive features include two LoopTracker LEDs (green for 
input, red for output) that vary in intensity with changes in the 
process input and output signals. These provide a quick visual 
picture of your process loop at all times and can greatly aid in 
saving time during initial startup and/or troubleshooting. 

Output Test 

An API exclusive feature includes the test button to provide a 
fixed output (independent of the input) when held depressed. 
The test output level is potentiometer adjustable from 0 to 
100% of output span. 
The output test button greatly aids in saving time during initial 
startup and/or troubleshooting.

How to Order

Please specify 

Model 
Input range (if factory is to pre-set) 
Output range (if factory is to pre-set) 
Options as required

Potentiometer Input

Field selectable ranges via switch settings 
See table for complete listing 
3 wire connection required
Minimum:

0-100

Maximum: 

0-1 M

Input span: 

10-100% of potentiometer range 

Input offset: 

0-90% in 10% increments

Input Impedance

10 M

 minimum

Common Mode Rejection

120 dB minimum

LoopTracker

Variable brightness LEDs indicate I/O level and status

DC Output Ranges

Field selectable ranges via switch settings 
See table for complete listing
Voltage: 

0-1 VDC to 0-10 VDC, 10 mA max 

Bipolar voltage:  ±5 VDC or ±10 VDC 
Current: 

0-2 mADC to 0-20 mADC 
20 V compliance, 1000 

 at 20 mA

Output Logic

Normal

Output Calibration

Multi-turn zero and span potentiometers 
±15% of span adjustment range typical

Output Loop Power Supply

20 VDC nominal, regulated, 25 mADC, <10 mV

RMS

 

max. ripple

May be selectively wired for sinking or sourcing mA output

Output Test

Front button sets output to test level when pressed 
Potentiometer adjustable 0-100% of span

Output Ripple and Noise

Less than 10 mV

RMS

Linearity

Better than ±0.1% of span

Ambient Temperature Range and Stability

–10°C to +60°C operating ambient 

Better than ±0.02% of span per °C stability

Response Time

70 milliseconds typical 
1 millisecond typical with DF option

Isolation

1200 V

RMS

 minimum 

Full isolation: power to input, power to output, input to output

Housing and Connectors

IP 40, requires installation in panel or enclosure 
For use in Pollution Degree 2 Environment 
Mount vertically to a 35 mm DIN rail
Four 4-terminal removable connectors, 14 AWG max wire size

Power

85-265 VAC, 50/60 Hz or 60-300 VDC, 2 W maximum 
D versions: 9-30 VDC or 10-32 VAC 50/60 Hz, 2 W maximum

Removable Plugs

Dimensions

0.89" W x 4.62" H x 4.81" D   
22.5 mm W x 117 mm H x 122 mm D  
Height includes connectors

Minute 

Setup!

1

Universal 

Power

Output LoopTracker 

LED

Input LoopTracker 

LED

Output Test 

Function

Front Zero and Span

Connect mA Output 

for Sink or Source

Use Any 

Potentiometer

Free Factory 

I/O Setup!

 H H H H H H

  H H H H H

H H H H H H

  H H H H H

 H H H H H H

  H H H H H

H H H H H H

  H H H H H

 H H H H H H

Made in USA

File E145968

85-265 VAC, 60-300 VDC 

model only

© 10-18

api-usa.com

1220 American Way Libertyville, IL 60048 
Phone: 

800-942-0315

 

Fax: 800-949-7502

A

BSOLUTE

 P

ROCESS

 I

NSTRUMENTS

1  2  3  4

5  6  7  8

9 10 11 12

13 14 15 16

See Wiring 

Diagrams on 

Next Page

Summary of Contents for APD 4008

Page 1: ...eatly aid in saving time during initial startup and or troubleshooting Output Test An API exclusive feature includes the test button to provide a fixed output independent of the input when held depressed The test output level is potentiometer adjustable from 0 to 100 of output span The output test button greatly aids in saving time during initial startup and or troubleshooting How to Order Please ...

Page 2: ...de approxi mately 50 output When the test button is depressed it will drive the output side of the loop with a known good signal that can be used as a diagnostic aid during initial start up or trou bleshooting When released the output will return to normal The Test Cal potentiometer can be used to set the test output to the desired level It is adjustable from 0 to 100 of the output span Press and ...

Page 3: ... 90 450V 458V 451V 456V 459V 452V 457V 453V 454V 455V 450I 458I 451I 456I 459I 452I 457I 453I 40 80 440V 448V 441V 446V 449V 442V 447V 443V 444V 445V 440I 448I 441I 446I 449I 442I 447I 443I 30 70 430V 438V 431V 436V 439V 432V 437V 433V 434V 435V 430I 438I 431I 436I 439I 432I 437I 433I 20 60 420V 428V 421V 426V 429V 422V 427V 423V 424V 425V 420I 428I 421I 426I 429I 422I 427I 423I 10 50 410V 418V 41...

Page 4: ...Clip Upper Mount Lower Mount B C D E Connections 3 4 9 10 11 13 16 Term Signal Sig Out Sig Out Full Scale Minimum Wiper Arm Power Power APD 4008 Potentiometer to DC Isolated Transmitter Output V I Input Output Offset Input Switch B Span Position 100 90 80 70 60 50 40 30 20 10 0 9 8 7 6 5 4 3 2 1 Offset Switch C Offset Position 0 10 20 30 40 50 60 70 80 90 0 1 2 3 4 5 6 7 8 9 Output Switch D Curren...

Reviews: