ABB | SACE Tmax XT
External electronic accessories | 11 - Ekip Signalling 2K
173 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
Output parameters
All the available inputs enable the following parameters to be configured:
Parameter
Description
Default
Signal source
Event which activates the output and switches the contacts.
Different protection proposals, statuses and thresholds are available on the
display; the Custom mode can be configured via Ekip Connect so as to
extend the solutions and combine several events
None
Delay
Minimum duration of the presence of the source before the output is
activated; the delay is given in seconds and can be set within range: 0 s to
100 s, in 0.01 s steps
NOTES
:
• the output will not be switched if the source is deactivated before
this time has elapsed
• if delay = 0 s the source must still be present for longer than 300 µS
0 s
Contact Type
Defines the rest status of the contact with source not present between:
open (NO) and closed (NC)
NO
Latched
Allows the output (and relative status led) to be kept activated (On) or
deactivated (Off) when the event disappears
OFF
min Activation
Time
Defines the minimum closing time of the contact following the rapid
presence of sources:
• Source duration < min. activation = contact is activated for the minimum
activation time
• Source duration
≥
min. activation = contact is activated for as long as the
source persists
Choose between: 0 ms, 100 ms, 200 ms
0 ms
About
The specific menu of the module available in the
About
-
Modules
menu contains:
• the serial number and version of the module
• the statuses of the inputs (On/Off) and outputs (Open/Closed)
Test
The test area in the
Test
menu is activated if the
Ekip Signalling 2K
module is detected correctly.
For details of the test characteristics, please consult page 134.
Remote information
Certain additional information concerning the version and status of the module is available via the service
connector (via Ekip Connect) or by communication via system bus; the information includes: HW and Boot
version, CRC status (correctness of the SW in the module).