ABB | SACE Tmax XT
Ekip Touch - Default | 1 - Ekip TOUCH default parameters
135 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
Ekip Touch - Default
1 - Ekip TOUCH default parameters
Foreword
Given the number of parameters available with Ekip Touch, each chapter describing their characteristics also
includes their default value settings.
The configurations of the main parameters are given below.
Protections
All Ekip Touch models are supplied with the protections (and relative correlated functions) off, with the
exception of the protections listed below:
Protection
Configuration
L
I1= 1 In; t1= 144 s; curve= t= k/I
2
; prealarm: 90% I1
I
I3= 4 In; startup= OFF
Harmonic distortion
On
Rc
(1
)
Idn= 3 A; Tdn= 0,06 s
(1)
protection available and active if model Rc Rating Plus is present
Parameters
Unless different specifications are requested when ordering, all Ekip Touch models are supplied with the
following configurations:
Parameters
Configuration
Frequency
50 Hz (IEC) / 60 Hz (UL)
Configuration
3P (3P circuit-breaker) / 4P (4P circuit-breaker)
Neutral
Off (3P circuit-breaker) / 50% (4P circuit-breaker)
Rated voltage
400 V
Power flow
Top
→
Bottom
Phase Sequence
1-2-3
Local bus
Off
Mode
Local
Language
English
Bluetooth Low Energy
Off
Password
00001
Home page
Histograms
Led Alive
Disabled
View
Horizontal
Maintenance
On
Test Bus
On
Modbus RTU par
Address: 247; baudrate: 19.2 Kbit/s
Profibus
Address: 125
DeviceNet
TM
MAC ID: 63; baudrate: 125 Kbit/s
Modbus TCP/IP
Static IP: 0.0.0.0