52
| XSERIES G5 START UP GUIDE | 2106001MNAA
9
Initial measurement application setup
The XFC or XRC shipped with standard configuration and the gas orifice
measurement application configured by default. This procedure describes
the setup of that flow measurement application (single tube). To set up
additional tubes, or for different measurement application types, refer to
the user manuals listed in
, the application
instructions, or click
Help
for online topics on the specific application
required.
Set up the gas orifice flow measurement application:
1.
On the PCCU navigation tree, click
Flow Measurement
>
Adv
Setup
.
Figure 9-1:
Flow Measurement
Advanced
Setup (Gas orifice)
.
2.
On the
Setup
tab, verify and change if necessary, the following
settings:
a.
If receiving live flowing temperature values from an RTD, set
the RTD Installed
field to
Yes
.
b.
If using a fixed temperature value instead of live readings, set
the Use Fixed Temperature field to
Yes.
i.
In the Fixed Temperature field, type the value for the fixed
temperature.
3.
On the navigation tree, click
Flow Measurement
>
Setup
.
4.
On the
General
tab, verify and change if necessary, the required
parameters: