![ABB VUBB Installation And Commissioning Manual Download Page 71](http://html.mh-extra.com/html/abb/vubb/vubb_installation-and-commissioning-manual_5265071.webp)
Installation and commissioning guide
1ZSC000562-AAK EN, REV. 2, 2019-07-03
71
4.
Remove the hose, and install the cover (1).
G004471
Torque
10 Nm
End of instruction
9.3 Transportation without transformer oil in the transformer
Overview
The tap-changer must be drained from transformer oil, if the transformer is drained.
Procedure
1.
Drain the transformer oil from the tap-changer.
CAUTION!
Do not transport the tap-changer filled with transformer oil if the transformer oil has been
drained from the transformer. This will help to prevent damage to the tap-changer.
End of instruction