For more information, see ...
Instruction
Step
Perform Asset registration in the
Administration
page of
Aurora Vision
®
Plant Portfolio Manager web interface.
8
Note:
You will need the product number of the gateway.
Verifying end-to-end data transfer (page 31)
Verify end-to-end data transfer using the Aurora Vision
®
Plant Portfolio Manager web portal.
9
Configuring Ethernet adapter modules of the solar inverters
Configure the FENA Ethernet adapter module to enable communication with the inverter.
1.
Install the FENA module. See instructions in
FENA Ethernet adapter module user's
manual
.
2.
Power on the inverter.
3.
Set parameter
150.31 FBA B Enable
=
Enable
.
4.
Configure adapter module parameters in parameter group
154 FBA B
. For example,
set the node address and the communication profile, typically
Transparent 16-bit
profile.
See the example configuration in the below screen. The configuration uses a private
network with IP address:
192.168.1.5
and network mask:
255.255.255.0
). For more
information, see
FENA Ethernet adapter module user's manual
(3AUA0000093568
[English]).
5.
Validate the settings with parameter
154.27 FBA B par refresh
=
Configure
.
20 Start-up