background image

2

AUTOM ATI C TR A N S FE R SWITCH E S , R E PL ACE M E NT OF S PA R E PA RTS

Additional information

We reserve the right to make technical 
changes or modify the contents of this 
document without prior notice. With  
regard to purchase orders, the agreed 
particulars shall prevail. ABB does not 
accept any responsibility whatsoever for 
potential errors or possible lack of infor-
mation in this document.

We reserve all rights in this document 
and in the subject matter and illustra-
tions contained therein. Any reproduc-
tion, disclosure to third parties or  
utilization of its contents – in whole or  
in parts – is forbidden without prior 
written consent of ABB.

Summary of Contents for TruONE ATS OXB250E3S3QT

Page 1: ...CE INSTRUCTION MECHANISM FRAME POWER AND CONTROL MODULES TruONE ATS Automatic transfer switches Replacement of mechanism and spare parts TruONE ATS Automatic transfer switches 34OX_MECH_ rev B 1SCC303018M0201 ...

Page 2: ... orders the agreed particulars shall prevail ABB does not accept any responsibility whatsoever for potential errors or possible lack of infor mation in this document We reserve all rights in this document and in the subject matter and illustra tions contained therein Any reproduc tion disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written...

Page 3: ...instruments used For more information questions or spe cific problems contact your nearest ABB representative Warning This manual is written for qualified per sonnel only and is not intended as a sub stitute for a proper course or experience about safety procedures for this device For the products equipped with commu nication the purchaser the installer or the final customer is responsible for ap ...

Page 4: ...ion equip ment ensure that the apparatus is in a safe condition and proceed in accordance with the Laws in force The maintenance operations must be car ried out by skilled personnel An electrical skilled personnel IEV 195 04 01 person with relevant education and experience to enable him or her to perceive risks and to avoid hazards which electricity can create ABB declines all liability for damage...

Page 5: ...REMARK See also Chapter 1 Removing complete mechanism from the switch 4 OX_30 400_ Replacing of frame power and control modules 18 REMARK See also Chapter 2 Replacing of complete mechanism with electronics 5 OX_400U 1600 Removing of frame control and power modules 23 REMARK See also Chapter 1 Removing complete mechanism from the switch 6 OX_400U 1600 Replacing of frame power and control modules 27...

Page 6: ...6 AUTOMATIC TR ANSFER SWITCHES REPL ACEMENT OF SPARE PARTS 6 1 Removing the complete mechanism from the switch OX_30 1600_ ...

Page 7: ...7 34OX _ MECH _ REV B 1SCC303018M0201 7 1 ...

Page 8: ...enclosure height mm width mm depth mm Use Cu Alconductors 60 C Wire only Suitable for use with terminal kit OZXA400 or OZXA400L 4x2 600 MCM Terminal torque 500 lb in 1180 560 217 400A RMS SYMM AMPS X1000 VOLTAGE MAX FUSE CLASS or CIRCUIT BREAKER MANUFACTURER TYPE AMPS MAX RMS SYMM AMPS X1000 VOLTAGE MAX TIME DURATION Sec 30 RMS SYMM AMPS X1000 VOLTAGE MAX TIME DURATION Sec gG 480 Automatic Transfe...

Page 9: ...AMECH 3 L2 OXAMECH 4 L2 Level 3 OXAMECH 2 L3 OXAMECH 3 L3 OXAMECH 4 L3 Level 4 OXAMECH 2 L4 OXAMECH 3 L4 OXAMECH 4 L4 Delayed transition I O II or II O I Level 2 OXBMECH 2 L2 OXBMECH 3 L2 OXBMECH 4 L2 Level 3 OXBMECH 2 L3 OXBMECH 3 L3 OXBMECH 4 L3 Level 4 OXBMECH 2 L4 OXBMECH 3 L4 OXBMECH 4 L4 Check the handle position in the new mechanism is same as the indication in the switch Use the handle if ...

Page 10: ...10 AUTOMATIC TR ANSFER SWITCHES REPL ACEMENT OF SPARE PARTS 10 2 1 Nm 8 75 lb in ...

Page 11: ...11 34OX _ MECH _ REV B 1SCC303018M0201 11 11 2 Configuration with Ekip Programming module by using Ekip Connect software ...

Page 12: ...12 AUTOMATIC TR ANSFER SWITCHES REPL ACEMENT OF SPARE PARTS 12 2 Click ...

Page 13: ...13 34OX _ MECH _ REV B 1SCC303018M0201 13 13 2 AUTO ...

Page 14: ...14 AUTOMATIC TR ANSFER SWITCHES REPL ACEMENT OF SPARE PARTS 14 3 See Chapter 1 to remove the mechanism from the switch OX_30 400_ Removing of frame control and power modules 3 2 1 ...

Page 15: ...ión esta transferencia es adecuada para utilizarse en un circuito capaz de liberar la corriente de contocircuito a la tensión máxima marcada Convient à la commutation de la charge totale ď un circuit si la charge de tungsten ne dépasse pas de 30 pourcent le couranr nominal du commutateur Le courant de charge continu ne doit pas dépasser de 100 pourcent le courant nominal du commutateur AVERTISSEME...

Page 16: ...R ANSFER SWITCHES REPL ACEMENT OF SPARE PARTS 16 3 Removing of power module Hazard Wait at least 60 seconds after removing the mechanism before disconnecting the connector to allow the capacitors to discharge Torx 20 ...

Page 17: ...17 34OX _ MECH _ REV B 1SCC303018M0201 17 3 ...

Page 18: ... SPARE PARTS 18 4 OX_30 400 Replacing of frame power and control modules Frame module Open transition I II OXAFRAME 2 Delayed transition I O II or II O I OXBFRAME 2 Power module Open transition I II and delayed transition I O I or II O I OXPOWER 400 ...

Page 19: ...19 34OX _ MECH _ REV B 1SCC303018M0201 19 4 Torx 20 1 Nm 8 75 lb in ...

Page 20: ...l module Open transition I II Level 2 OXACONTROL 400 L2 Level 3 OXACONTROL 400 L3 Level 4 OXACONTROL 400 L4 Delayed transition I O II or II O I Level 2 OXBCONTROL 400 L2 Level 3 OXBCONTROL 400 L3 Level 4 OXBCONTROL 400 L4 Apply warning label on top of the closed connector ...

Page 21: ...21 34OX _ MECH _ REV B 1SCC303018M0201 21 4 Torx 20 1 Nm 8 75 lb in ...

Page 22: ...22 AUTOMATIC TR ANSFER SWITCHES REPL ACEMENT OF SPARE PARTS 22 4 ...

Page 23: ...23 34OX _ MECH _ REV B 1SCC303018M0201 5 See Chapter 1 to remove the mechanism from the switch OX_400U 1600 Removing of frame control and power modules 3 2 1 ...

Page 24: ...a continuación esta transferencia es adecuada para utilizarse en un circuito capaz de liberar la corriente de contocircuito a la tensión máxima marcada Convient à la commutation de la charge totale ď un circuit si la charge de tungsten ne dépasse pas de 30 pourcent le couranr nominal du commutateur Le courant de charge continu ne doit pas dépasser de 100 pourcent le courant nominal du commutateur ...

Page 25: ...25 34OX _ MECH _ REV B 1SCC303018M0201 5 ...

Page 26: ...26 AUTOMATIC TR ANSFER SWITCHES REPL ACEMENT OF SPARE PARTS 5 Torx 20 long min 140 mm Removing of power module ...

Page 27: ... 1600 Replacing of frame power and control modules Frame module Open transition I II OXAFRAME 3 OXAFRAME 4 Delayed transition I O II or II O I OXBFRAME 3 OXBFRAME 4 Power module Open transition I II and delayed transition I O I or II O I OXPOWER 1600 ...

Page 28: ...28 AUTOMATIC TR ANSFER SWITCHES REPL ACEMENT OF SPARE PARTS 6 ...

Page 29: ...n 140 mm 1 Nm 8 75 lb in Control module Open transition I II Level 2 OXACONTROL 1600 L2 Level 3 OXACONTROL 1600 L3 Level 4 OXACONTROL 1600 L4 Delayed transition I O II or II O I Level 2 OXBCONTROL 1600 L2 Level 3 OXBCONTROL 1600 L3 Level 4 OXBCONTROL 1600 L4 ...

Page 30: ...tat de la source d alimentation avant un transfert manuel Une opération manuelle peut entraîner un transfert déphasé si les deux sources sont sous tension COURANTSNOMINAUXDERÉSISTANCEAU COURT CIRCUITETDEFERMETUREDECIRCUIT ETCOURANTSNOMINAUXDECOURTEDURÉE POURDESDISJONCTEURSSPÉCIFIQUES De commutateur s il est protégé par un disjoncteur dont le nom du fabricant le type et le courant nominal sont indi...

Page 31: ...31 34OX _ MECH _ REV B 1SCC303018M0201 ...

Page 32: ... Contact us ABB Oy P O Box 622 FI 65101 Vaasa Finland abb com lowvoltage Copyright 2018 ABB All rights reserved Specifications subject to change without notice 34OX_MECH_ rev B 1SCC303018M0201 11 6 2019 ...

Reviews: