41/72
TLE Series 625 to 1000 PurePulse™ UL S2
UPS Installation Guide / REV-B
4.9
Wiring connection
Note!
UPS installation and connection must be performed only by an ABB Service Technician!
Refer to the “Safety prescriptions - Installation” described on Chapter 1.
In case of UPS equipped with options or customized parts not covered by this manual, please
consult the appropriate technical documentation before proceeding with electrical connections.
Carefully read the following recommendations before proceeding:
•
Ensure that the AC and DC external isolators are Off and prevent their inadverted operation.
•
Do not close any external isolators prior to the commissioning of the equipment.
•
The input/output cables must be connected in clockwise phase rotation for both Bypass and Rectifier Input
Bars if separate, taking care to avoid risk of short circuit between different poles.
•
The grounding and neutral connection of the electrical system must be in accordance with local regulations.
•
In case of additional cabinets containing Batteries, input/ output transformers, etc, their ground terminals
must be connected to the UPS main ground terminal.
•
Once the power cables have been connected, re-install the internal safety shields and close the cabinets by re-
installing all external panels.
TLE Series 625 & 750 Access to the bus bars for the cable connections
Fig. 4.9-1 TLE Series 625 & 750 - Access to connection bus bars
To access Input, Output and Battery connections
proceed as follows:
•
Remove the front protection panels “
A
&
B
”.
•
Top cable entry: remove the plates “
C
&
D
”.
•
Bottom cable entry: remove the plates “
E
&
F
”.
Note!
For UPS correct operation, the input
mains phase rotation must be clock-wise.
Note!
Drill the cover plate “
C - D - E - F” appropriate holes for cable entry. See drawing “1” for details.
The holes must be drilled with the cover plate “C - D - E - F” removed from the UPS to avoid metal
dust falling in the connection bars area.
E
PO
E
PO
-
+
1
2
Q1
0 OFF
I O
N
D
Top entry cables
Battery
C
Top entry cables
Utility input & Load output
Bottom entry cables
Utility input & Load output
E
!
Please remove
the plates (C-D-E-F)
before drilling any wholes
Bottom entry cables
Battery
F
A
B
TLES_UL_
625-750_S
2_UPS con
nection_A
BB_01US