TERRA DC WALLBOX UL
2020-10-05
29/38
2. Push the cables back through the gland plate, until sufficient cable length is left to reach the cable
terminals. Ensure the PE cable is longer than the other cables.
3.
Slide the cable cover and tighten the two screws.
If a wired internet connection is not used, please ensure the cable entry hole is closed, to assure the
IP54 grade of the cabinet, and prevent insects and small animals to enter the cabinet.
5.5
Connect cables
5.5.1
Connect PE of power cable
Preconditions:
•
Tools: Wire stripper pliers; wire-end lug pliers; wire-end lug.
DANGER
Hazardous voltage
Make sure that the main switch of the power supply group for the
product is set to the OFF position. Perform a voltage check and
make sure that the electrical power is disconnected from the sys-
tem. Follow recommended
NFPA-70e
procedures.
1.
Cut the PE wire of the power cable to the correct length (longer than the other phases) to reach the
PE connector.
Conduit
Installation
1.25“ secured to
bottom
mounting area.
1-phase Version
Shown
3-Phase Connection using flexible