76
“Operation and installation manual”
EN
10.2 Cable specifications
AC Input
AC cable cross section
350 MCM (copper) each phase (recommended)
AC connection type
M10 (
25/64
) cable lug
AC cable diameter (cable entry plate)
53/64
...1
37/64
in (21...40 mm)
Insulation
PVC or other material that is serviceable for
outdoor, UV-protected and suitable for use in
underground ducts
Protective Earth (PE)
PE cable cross section
Select the Ground (PE) wire size per NEC or local
electric code
PE connection type
M12 (
15/32
) cable lug
PE cable diameter (cable entry plate)
53/64
...1
37/64
in (21...40 mm)
Insulation
PVC or other material that is serviceable for
outdoor, UV-protected and suitable for use in
underground ducts
Ethernet
CAT
CAT 5e (recommend)
CAT 6 (high presence of electromagnetic
interference and/or noise)
Ethernet cable diameter (cable entry plate)
25/64
...
43/64
in (10...17 mm)
Insulation
PVC or other material that is serviceable for
outdoor, UV-protected and suitable for use in
underground ducts
Tilt sensor (option)
Number of wires
4 (2 wires for power supply and 2 wires for relay
contacts)
Max. Wires cross section
12 AWG (4 mm
2
) without ferrule
14 AWG (2.5 mm
2
) with ferrule
Cable diameter (cable entry plate)
25/64
...
43/64
in (10...17 mm)
Insulation
PVC or other material that is serviceable for
outdoor, UV-protected and suitable for use in
underground ducts
10.3 Torque specification
Parameter
Specification
Fasteners for the PE wire
442.5...663.8 lbf-in (50...75 Nm)
Fasteners for the L1, L2, L3
292...389 lbf-in (33...44 Nm)
Tilt sensor screw terminal block
11.5 lbf-in (1.3 Nm)
Fasteners for the connection of the EVSE to the base
(M12 bolt)
177 lbf-in (20 Nm)