
70
“Operation and installation manual”
EN
9.3.6 Safety equipment and tools
The below table shows the required tools and equipment’s that are necessary to perform the steps of the total
de-energization procedure.
NOTE
For safety reasons, service engineers shall check the functionality of the tools before start of work.
Tools and Equipment
Description
Voltage detector (EN 61243-2)
Duspol Digital 1,2kVdc 1kVac (suggested)
Safety tags “DO NOT OPERATE”
Safety tags “DO NOT OPERATE” with identification data (Name -
Company - P. Ph number)
Safety Padlocks
Padlocks used to secure the Lockout Tagout device in place.
Grounding kit (IEC 61230)
Suggested kit composition:
• Dehn: KFP 20 M10 (p/n: 754205)
• Dehn: KFP 20 M12 (p/n: 754200)
• Dehn : KKH 20 FS (p/n: 772312)
• Dehn: UK 25 SK (p/n: 773 034)
• Dehn: EKV4u1 16 G (four poles earthing and short-circuiting device)
9.3.7 Total de-energization procedure
1. Preliminary control
:
Make sure that the unit must be turned on.
2. Identification of AC external main source
:
Clearly identified the external AC main breaker with the plant manager cooperation and, if necessary, by
functionality test of it.
3. Operate the main AC external source isolation and secure
:
Turn off the external AC main breaker and carry out a LOTO.
4. Functionality check
:
Check that the charger is shut down.
5. Operate the main AC external breaker
:
Turn off the external AC main breaker.
6. Main Voltage absence check
:
Check the absence of voltage below the main breaker of the EVSE, using the dedicated holes
(A)
.
The verification must be carried out through the dedicated holes
(A)
in the Main AC protection barriers
(41)
,
using the voltage detector by checking between phases to ground and respectively between them.
A
41