SMART POSITIONER
CALIBRATION
A
-
7
Input A-to-D Calibration
This procedure applies to Positioner configured for either
ANALOG
or
DIGITAL
. Any differences between the two are noted in the
Com-
ments
column.
Key
Display
Comments
This operation will cause a change in output not cor-
responding to the input. Be sure the control loop is in
manual.
Select
YES
.
Select
INPUT A/D CAL
.
Make the proper adjustments and press
.
NOTE:
Refer to Positioner instruction for details on
the calibrations.
Make the proper adjustments and press
.
NOTE:
Refer to Positioner instruction for details on
the calibrations.
C A LI-
B R AT E
OUTPUT WILL BE
AFFECTED! PROCEED?
NO
→
YES
E N T E R
OUTPUT D/A CAL
→
INPUT A/D CAL
MAN POSITION CAL
AUTO POSITION CAL
E N T E R
APPLY 4 mA
TO INPUT
THEN HIT ENTER
ENTER
E N T E R
APPLY 20 mA
TO INPUT
THEN HIT ENTER
ENTER
E N T E R
ID TAGNAME
READY