background image

9AKK106930A0651 - Oct 2016 - Revision 5

Copyright © 2016 ABB
All rights reserved

ABB Australia Pty Limited

Phone: 1300 666 595
Fax: 1300 666 594
E-mail: [email protected]

www.stanilite.com.au

For Nexus LX; unplug the data cable connection. When the fitting is reconnected to the supply, it will need time to 
recharge its battery for 24 hours before it will be capable of a full length discharge again.

Testing precautions

Once the fitting is permanently connected to the mains supply, a commissioning discharge test as required in    
AS/NZS2293.2 must be carried out. You will need to allow 24 hours for the battery to fully charge prior to conducting 
this test, presently (at the time of writing), the standard requires that fittings operate in emergency mode for a period not 
less than 2 hours for their commissioning test and for not less than 90 minutes thereafter (it is required that 6 monthly 
discharge tests be carried out). You will need to keep the records for the commissioning test and enter them into the 
building emergency services logbook or via other recording methods as allowed by AS/NZ2293.2.

Construction sites

Continuously switching of the mains power supply that is connected to emergency light fittings during the construction 
phase of an installation will cause these fittings to discharge and charge their batteries many times over a short period; 
this can shorten the life of the battery and will also result in shortened emergency lamp life. ABB does not recommend 
such practices and may not honour the warranty on batteries when they are subjected to such harsh operating 
conditions. Emergency light fittings are designed to be discharge tested once every 6 months as per AS/NZS2293.2, 
subjecting the product to repeated discharge or charge cycles is regarded as an abuse of the fittings.

Trouble shooting guide

If you have installed and connected the unit as per the instructions listed earlier and it does not function correctly, use the 
following table as a guide to fixing the problem. Look up the type of fault in the left column and check the possible causes 
from the right column.

If the unit still does not work after checking these possible causes, contact ABB service in Australia on 1300 666 595, 
Monday to Friday, 7.00am to 5.00pm (AEST) and ask for help. Our trained service personnel will usually be able to 
take your call immediately and assist you in resolving your difficulty. ABB is committed to providing valuable through-life 
support for its products. 

Congratulations

Congratulations on choosing to use this ABB product covered by our unique through-life support system. This document 
is designed to assist you during the installation of this product; for the safety of yourself and others 

ABB recommends 

that you read this document thoroughly before commencing installation

. The fittings are designed for easy 

installation. They are advanced pieces of electronic equipment which, when treated with care and maintained through 
regular and appropriate servicing, will perform reliably for many years to come.

Safety warning

In Australia and New Zealand, only licensed electricians are permitted by law to work with 240 volt electrical installations.
Do not attempt to install or connect this product unless you are a licensed electrician.
Turn off and isolate the electrical supply before connecting this fitting to the building wires.
Do not touch the terminals of the terminal block when the light fitting is energised.
The only user-serviceable parts are fluorescent or halogen lamp/s. LED light sources are not user-servicable.
Do not tamper with the fitting or the warranty will be void.
As the installer, it is your responsibility to ensure compliance with all relevant building and safety codes, (ie: AS3000,  
AS/NZS2293). Refer to the applicable standards for data and mains cabling installation procedures and requirements.

Important note: This product is designed for indoor and outdoor use.

Nexus LX (data cable system)

The Nexus

®

 range of emergency light fitting are designed to be connected together into a special communication network 

over a Level 4 (or higher) high speed, single twisted pair data cable. The Nexus user and technical guide describes all 
you need to know to successfully install a Nexus project. Ask for it from your supervisor, from your employer or from your 
nearest ABB product supplier. The network cabling of the building must be installed as per the procedure detailed in the 
Nexus user and technical guide. No mains or mains carrying cables are to be connected to the data terminals or cables.

Nexus RF (wireless system)

The Nexus RF range of light fittings are designed to communicate via a proprietary RF network, however the electrical 
installation of the fittings is identical to that of a standard non-monitored fitting.

Doc no. 29-99570

Batten weatherproof emergency
Standard, Nexus LX, Nexus RF

Installation manual

No.

Fitting type

Fault

Possible causes

1

Standard

Nexus LX

Nexus RF

Lamp does not light up when connected to mains

AC supply not connected or turned off; or

Switch active turned off; or

Lamp damaged or not inserted properly

2

Nexus LX

LED is flashing green but AC lamp does not come on 

when connected to mains

Switch active turned off; or

Lamp damaged or not inserted properly; or

Missing loop from unswitched to switched active

3

Nexus LX

LED is flashing green but lamp does not come on when 

test switch is pressed

Switch active turned off; or

Lamp damaged or not inserted properly; or

Battery pack not connected or faulty; or

Test switch damaged

4

Nexus LX

LED does not light up red after the commissioning

Battery pack not connected; or 

LED wire not properly inserted into the terminal

5

Standard

Nexus LX

Nexus RF

Lamp is lit momentarily when test switch is pressed or 

when mains fail

Battery not fully charged (allow up to 24 hours); or

Battery pack damaged

6

Nexus LX

LED is constant green

Unit self checks fail - return to manufacturer

7

Nexus LX

Nexus RF

Unit LED is not flashing yellow/orange under wink node 

command

Unit is not receiving communication signal

Check data cable wiring path and cable or RF 

connections

Refer to Nexus user and technical guide

This document covers

What’s inside the box

Safety warning

Batten weatherproof

Installation instructions

Installation manual

Removal instructions

Warranty information

Testing precautions

Trouble shooting guide

Reviews: