Electrical connections
14 Sensyflow
FMT700-P
42/14-42-EN
Pos: 8.8 /Technische Daten / Datenblatt/Durchfluss/FMT700-P/Elektrischer Anschluss/SLOT 4: D-SUB-Stecker „Analogausgänge“ @ 33\mod_1251878296252_3101.doc @ 298759 @ 2
3.4
SLOT 4: D-SUB connection „Analog Outputs“
Pin
Assignment
Pin
Assignment
1 GND
14
I
out GND
2
I
out+
15
U
out GND
3
U
out+
16 GND
4
Flowmeter sensor coding
17
Flowmeter sensor coding
5
Nominal diameter coding
18
Nominal diameter coding
6
Nominal diameter coding
19
Nominal diameter coding
7
Free coding
20
Free coding
8
Free coding
21
Free coding
9 -
22
-
10 -
23 -
11
Temp. 1 +
24
Temp. 1 -
12
Temp. 2 +
25
Temp. 2 -
13
GND
ext.
G00925
25
14
13
1
Fig. 11: Terminal connection of 25-pole D-SUB connection „Analog Outputs”
Digital coding of the flowmeter sensor
Sensyflow FMT700-P
User
The outputs are connected as „open collectors“.
Technical data
Collector-emitter-voltage
5 ... 24 V DC
Load resistance R
L
min.
2 k
Ω
Log. level 0
= U
ext.
Log. level 1
= e. g. approx. 0.8 V
(at +15 V U
ext.
; negative logic)
G00926
R
L
R
L
R
L
Bit 1
Bit 2
Bit 3
U
ext.
R
2 k
U
= 5 ... 24 V DC
L
ext.
?
W
GND
ext.
Fig. 12: Terminal connection of open-collector outputs for flowmeter sensor coding