ScreenMaster RVG200
Paperless recorder
7 Configuration
72
OI/RVG200-EN
7.7.4 Date and time
Time
Date and time
Set the date and time formats and set the current date and time using a
dialog box.
Note.
If daylight saving is required, enter the settings (see next page)
before
setting the time and date as the operation of the internal
clock is affected by the daylight saving settings.
Changing the date and time causes the recording to be disabled
until the
Configuration
level is exited.
Changes to the date and time are effective immediately
in the
dialog box is touched. Touch
in the dialog box to exit date and
time setup without saving changes. Touching
when exiting the
Configuration
level (see Fig. 7.7, page 66)
does not
reset the clock
to its previous setting.
Setting an earlier date or time results in the loss of all data currently
in the internal buffer memory past that date. Data archived to
external media is unaffected. If an earlier time must be set, change
the
Instrument Tag
(see page 69). This causes new archive files to
be created and the duplicated hour of data is then saved to the
new files.
Time changes due to automatic daylight saving do not affect the
recorded data.
If the
status icon is displayed the clock battery must be
replaced – contact the Company.