Create new I/O signals using name prefix
: Enter the signal prefix to
be used in signal names. Not mandatory.
Note
If this field is left empty, no signals will be added to the configuration.
Select
OK
. The I/O device, and its signals, are added.
5 Restart the controller.
Updating an existing I/O device
When an add-on I/O device has been attached or removed, the I/O configuration
of the base I/O device must be updated.
Note
Always attach or remove I/O devices from the right side of the base I/O device,
otherwise the optical link is broken.
The update function can also be used for the generation of default signals on a
device.
1 Start RobotStudio and connect to the OmniCore controller. Request write
access.
2 The add-on I/O device is attached or removed from the base module. The
modified I/O device appears.
xx2100000078
3 Right-click the modified I/O device and select
Configure
.
Or
Continues on next page
60
Application manual - Scalable I/O
3HAC070208-001 Revision: F
© Copyright 2019-2022 ABB. All rights reserved.
4 Software commissioning
4.3 Configuring Scalable I/O devices using RobotStudio
Continued