ABB | SACE Tmax XT
52 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
Protections | 2 - Voltage protections
OV2 Protection
U16
t
t16
V
OV2
Function
OV2 protection functions in the same way as OV protection: the protection sends a TRIP command if one or
more line-to-line voltages detected by the unit exceed threshold U16 for longer than t16.
To check and simulate the trip times in relation to all the parameters, please consult:
• summary table of the protections with the operating characteristics (page 80)
• the graph with trip curve (page 89)
Parameters
Parameter
Description
Default
Enable
Activates/deactivates the protection and its availability in the parameters
menu
OFF
Trip Enable
Activates/deactivates transmission of the open command: if disabled, the
alarm and exceedance of protection time are only managed as information
OFF
Threshold
U16
Establishes the value that activates the protection.
The value is given as both absolute value (Volts) and relative value (Un) and
can be set within the range: 1 Un to 1.5 Un in 0.001 Un steps
1,05 Un
Time t16
This is the trip time of the protection; the value is given in seconds and can
be set within a range: 0.05 s to 120 s, in 0.01 s steps
5 s
Limitations and additional functions
The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
connection to the system bus (page 75).
Phase sequence
The
Phase Sequence
protection trips when the sequence of line-to-line voltages is not aligned with the
sequence set by the user.
The required sequence can be set in the
Settings
menu and the protection activated in the
Advanced
menu
(page 33 and page 31).
VU Protection
U14
t
t14
V
VU
Function
The protection trips if the line-to-line voltages read by the unit are unbalanced; the protection sends a TRIP
command if the detected unbalance exceeds threshold U14 for longer than t14.
The protection excludes itself if the maximum value of the line-to-line voltage is less than 0.3 Un
To check and simulate the trip times in relation to all the parameters, please consult:
• summary table of the protections with the operating characteristics (page 80)
• the graph with trip curve (page 89)
Parameters
Parameter
Description
Default
Enable
Activates/deactivates the protection and its availability in the parameters
menu
OFF
Trip Enable
Activates/deactivates transmission of the open command: if disabled, the
alarm and exceedance of protection time are only managed as information
OFF
Threshold I14
Establishes the unbalance value that trips the protection.
Unbalance is expressed in percentage value and is calculated in the
following way: % Unba = 100 x (Δmax U
mi
) / U
mi
in range: 2% to 90% in 1%
steps.
NOTE
: Δmax U
mi
: maximum deviation among the three voltages
calculated by comparing each line-to-line voltage with the mean value;
U
mi
: mean value of the line-to-line voltages
50 %
Time t14
This is the trip time of the protection; the value is given in seconds and can
be set within a range: 0.5 s to 60 s, in 0.5 s steps
5 s
Limitations and additional functions
The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
connection to the system bus (page 75).