ABB SACE

SACE PR010/T

RH0029002

L2551

EN

SACE PR010/T

test unit annex

Summary of Contents for SACE PR111

Page 1: ...ABB SACE SACE PR010 T RH0029002 L2551 EN SACE PR010 T test unit annex ...

Page 2: ...ration 6 3 SACE PR212 MP protection release 8 3 1 Operation mode menu tree 9 3 2 Indications on operation 10 4 SACE PR222DS protection release 12 4 1 Operation mode menu tree 13 4 2 Indications on operation 14 5 SACE PR222MP protection release 15 5 1 Operation mode menu tree 16 5 2 Indications on operation 16 6 SACE PR223EF protection release 18 6 1 Operation mode menu tree 19 6 2 Indications on o...

Page 3: ...enu tree 23 8 3 Indications on operation 23 9 PR112 P and SACE PR112 PD protection release 24 9 1 Version with key last letter in serial number A D 24 9 2 Version without key last letter in serial number M Z 24 9 3 Operation mode menu tree 25 9 4 Indications on operation 26 10 PR112 P A and SACE PR112 PD A protection release 27 10 1 Operation mode menu tree 28 10 2 Indications on operation 29 11 S...

Page 4: ...ual Test 37 13 3 3 Trip test 37 13 4 Measurements 38 13 5 History 38 13 6 Configurations parameters 39 13 6 1 Configurations 39 13 6 2 Parameters 41 13 7 Information 42 13 8 Status 42 14 SACE PR122 P protection release 43 14 1 Operation mode menu tree 44 14 2 Indications on operation 46 14 3 Test 47 14 3 1 Automatic test of the release PR122 P 48 14 3 2 Manual Test 49 14 3 3 Trip test 49 14 3 4 Si...

Page 5: ...peration mode menu tree 56 15 2 Indications on operation 59 15 3 Test 59 15 3 1 Automatic test of the release PR123 P 60 15 3 2 Manual Test 61 15 3 3 Trip test 61 15 3 4 Sign mod autotest 61 15 3 5 Force output S ZS 61 15 3 6 Force output G ZS 61 15 3 7 Release output ZS 61 15 3 8 RC Test 62 15 4 Measurements 62 15 5 History 62 15 6 Configurations parameters 63 15 6 1 Configurations 63 15 6 2 Para...

Page 6: ...l IEC versions SACE PR112 in all IEC versions SACE PR113 in all IEC versions SACE PR111 A in all UL versions SACE PR112 A in all UL versions SACE PR113 A in all UL versions SACE PR121 in all versions SACE PR122 in all versions SACE PR123 in all versions SACE PR212 P with test connector on the front SACE PR212 MP with test connector on the front SACE PR222DS in all versions SACE PR222MP in all vers...

Page 7: ...te report 2 Manual 1 Default setting Start test 2 User setting Set parameters Start test 2 Reading 1 Ammeter Read currents 2 Config Param 1 DUT configurationand param 1 Manual parameters Display DUT configuration and parameters 2 Electronic parameters Display DUT configuration and parameters 2 Default parameters 1 Only for test Display default configuration and parameters 2 Operative Display defau...

Page 8: ... P NOTE the data indicating the type of CB and protection the rated current of the CTs and the Neutral setting are automatically identified by the PR010 T In this example protection function S is tested with curve t k threshold I2 1 00 In curve t2 0 5s supplying a fault current equivalent to 2 times the rated current In WARNING Config not valid 1 Set the PR212 P in Manual mode with I1at 1In curve ...

Page 9: ...ng the arrow keys set I F 2 00 11 Select the phase or phases on which to simulate the fault current L1 L2 L3 12 Press ENTER to activate fault simulation S PROT t k ON I2 1 0 In 400 A T2 0 5 s I f 2 00 800 A In this example the automatically identified rating of the current sensor is 400A ...

Page 10: ...arameters Display DUT configuration and parameters 2 Def parameters in PR010 T 1 Only for test Display DUT default configuration and parameters 2 Operative Display DUT default configuration and parameters 3 Inputs Read inputs 4 Tripping parameters Display tripping parameters 5 Information Read release identification SW version and Serial Number 3 Programming 1 Change DUT config par 1 DUT configura...

Page 11: ...where only the test current and the phase on which it is to be applied must be set If the PTC for protection against overtemperature is not present during the tests it is necessary to set the Input dip switch as the generic input Input 0 1 The Welded contacts WC input has to be at 0V no alarm during the tests At the end of each test the PR010 T unit waits until the thermal memory has returned to z...

Page 12: ...of the CTs are automatically identified by the PR010 T test unit In this example all the protection functions implemented by the SACE PR212 MP release are tested automatically 1 Set the PR212 MP in electronic set mode ELT 2 From the main menu select 1 Operation mode 3 Select the PR212MP unit with x PR212 MP 4 Select the type of activity with 1 Test 5 Select the type of test with 1 Protections 6 Se...

Page 13: ...ABB SACE SACE PR010 T RH0029002 L2551 12 67 67 4 SACE PR222DS protection release ...

Page 14: ...ameters 3 Default parameters 1 For test Display default test parameters 2 Operative Display default operative parameters 4 Communication par Display communication parameters for system bus 5 Information Read release identification SW version and Serial Number 3 Programming 1 Parameters Change DUT protection parameters Store protection unit parameters 2 Default download Program DUT with default ope...

Page 15: ...rameters must be performed only by con figuring the release in Electronic SET ELT with the dip switch provided The manual test may be performed either with Electronic SET or with manual SET In the case of manual test with manual SET thresholds and curves must be selected with the dip switches on the protection they are automatically updated on the display of the PR010 T unit where only the test cu...

Page 16: ...lease are tested automatically 5 SACE PR222MP protection release 1 From the main menu select 1 Operation mode 2 Select the PR222DS unit with x PR222DS 3 Select the type of activity 1 Test 4 Select the type of test 1 Protections 5 Select the test mode with 1 Automatic 6 Pressing ENTER enables a simulation of the failure for each protection function ...

Page 17: ...ameters Display DUT configuration and parameters 2 Electronic parameters Display DUT configuration and parameters 2 Def parameters in PR010 T 1 Only for test Display DUT default configuration and parameters 2 Operative Display DUT default configuration and parameters 3 Inputs Read inputs 4 Tripping parameters Display tripping parameters 5 Information Read release identification SW version and Seri...

Page 18: ...ic input Input 0 1 The Welded contacts WC input has to be at 0V no alarm during the tests At the end of each test the PR010 T unit waits until the thermal memory has returned to zero before proceeding with any subsequent tests in order to avoid any overlap in operation between the function being tested and the overload function L For the test on the protection function against locked rotor R the P...

Page 19: ...PR223EF protection release 1 Set the PR222MP in electronic set mode ELT 2 From the main menu select 1 Operation mode 3 Select the PR222MP unit with x PR222MP 4 Select the type of activity with 1 Test 5 Select the type of test with 1 Protections 6 Select the test mode with 1 Automatic 7 Pressing ENTER enables a simulation of the failure for each protection function ...

Page 20: ...rs 2 DUT parameters Display protection parameters 3 Default parameters 1 For test Display default test parameters 2 Operative Display default operative parameters 4 Communication par Display communication parameters for system bus 5 Information Read release identification SW version and Serial Number 3 Programming 1 Parameters Change DUT protection parameters Store protection unit parameters 2 Def...

Page 21: ...ng test reading or programming operations CB type and CT current rating are not yet defined the following message will be displayed Example of an automatic test application on the PR223EF release NOTE the data indicating the type of CB and protection the current rating of the CTs and the neutral setting are automatically identified by the PR010 T test unit In this example all the protection functi...

Page 22: ...the PR111 P protection unit as follows 7 2 Operation mode menu tree Protection function Threshold Curve L 0 4 x In B S 3 x In C I2 t k I 8 x In G 0 8 x In B 1 2 3 4 5 6 7 1 Operation mode 1 Select DUT PR111 1 Protections 1 Automatic Start test Create report 2 Manual Set parameters Start test 2 I inst protection Start test In InN In 2 Nr I1 xIn I2 xIn I3 xIn I4 xIn I G L S R P 1 1 1 TEST TOP ...

Page 23: ...esting as shown under the heading Default setting for automatic PR111 P testing 8 SACE PR111 P A protection release 1 From the main menu select 1 Operation mode 2 Select the PR111 unit with 1 PR111 3 Select the version of the PR111 with 2 PR111 LSI 4 Enter 1 to select the Neutral setting Neutral 50 5 Enter 2 to select the type of CB E1B12 6 Select the current rating of the CTs fit ted with 3 800 A...

Page 24: ...matic testing as shown under the heading Default setting for automatic PR111 P A testing Protection function Threshold Curve L 0 4 x In B S 3 x In C I2 t k I 8 x In G 0 4 x In B 1 2 3 4 5 6 7 1 Operation mode 4 Select DUT PR111 A 1 Protections 1 Automatic Start test Create report 2 Manual Set parameters Start test 2 I inst protection Start test 1 From the main menu select 1 Operation mode 2 Select...

Page 25: ...12 PD protection release 9 1 Version with key last letter in serial number A D 9 2 Version without key last letter in serial number M Z InN In 2 SACE PR112 PD RESET O L S I G TEST Nr In up Fault READ COMMUNICATION Vaux up Fault NETWORK EDIT EMERGENCY WARNING ESC TEST TOP ...

Page 26: ...efault parameters 1 Only for test 1 DUT config Display DUT default config 2 DUT parameters Display DUT default param 2 Operative 1 DUT config Display DUT default config 2 DUT parameters Display DUT default param 3 Information Read release identification SW version and Serial Number 3 Programming 1 Change DUT parameters 1 DUT config Change DUT configuration parameters 2 DUT parameters Change DUT pr...

Page 27: ...et it at 0 4xIn during the test phase The test current is equal to 2 5 times the threshold current In the case of manual mode the test current is 1 5xIn It is possible that after a test with trip on G protection function other trips of the protection will occur during the next 2s Contact wear for PR112 During testing on the PR112 with timing before trip higher than 10s there could be an increase i...

Page 28: ... menu select 1 Operation mode 2 Select the PR112 unit with x PR112 3 Select the M Z version 2 PR112 M Z 4 Select the type of activity with 1 Test 5 Select the type of test 1 Protections 6 Select the test mode 2 Manual 7 Select the type of setting used to test the protections 2 User setting 8 Select the protection function to be tested 3 I protection test 9 Using the arrow keys fill in the page dis...

Page 29: ...ult configuration 2 DUT protection parameters Display DUT default parameters 2 Operative 1 DUT configur Display DUT default configuration 2 DUT protection parameters Display DUT default parameters 3 Information Read release identification SW version and Serial Number 3 Programming 1 Change DUT parameters 1 DUT configur Change DUT configuration parameters 2 DUT parameters Change DUT configuration p...

Page 30: ...ly identified by the PR010 T test unit In this example protection function S is tested with curve t k threshold I2 1 20 In curve t2 0 4 s supplying a fault current equivalent to 2 times the rated current In 1 From the main menu select 1 Operation mode 2 Select the PR112 A unit with x PR112 A 3 Select the type of activity with 1 Test 4 Select the type of test with 1 Protections 5 Select the test mo...

Page 31: ... Active Power Read active power 2 Reactive power Read reactive power 3 Apparent power Read apparent power 4 Energy counters Read energy counters 5 Power factors Read power factors 6 Freq peak factor Read Freq peak factor 7 Last trip Read last trip 8 Config Param 1 DUT configur Display DUT configuration 2 DUT parameters 1 Protection parameters Read protection parameters 2 Other parameters Read othe...

Page 32: ...ly identified by the PR010 T In this example all the protection functions implemented by the SACE PR113 P and SACE PR113 PD release are tested automatically 1 Operation mode 2 Select DUT PR113 3 Programming 1 Change DUT config parameters 1 DUT config Change DUT configuration parameters 2 DUT param 1 Protection parameters Change DUT protection parameters 2 Other parameters Change other parameters 2...

Page 33: ...wers 1 Active Power Read active power 2 Reactive power Read reactive power 3 Apparent power Read apparent power 4 Energy counters Read energy counters 5 Power factors Read power factors 6 Freq peak factor Read Freq peak factor 7 Last trip Read last trip 8 Configuration param 1 DUT configur Display DUT configuration 2 DUT parameters 1 Protection parameters Read protection parameters 2 Other paramet...

Page 34: ...y identified by the PR010 T In this example all the protection functions implemented by the SACE SACE PR113 P A and SACE PR113 PD A release are tested automatically 1 Operation mode 2 Select DUT PR113 A 3 Programming 1 Change DUT config parameters 1 DUT config Change DUT configuration parameters 2 DUT param 1 Protection parameters Change DUT protection parameters 2 Other parameters Change other pa...

Page 35: ...mation 6 Status 1 Test 1 Start automatic test Test report 2 Start manual test Test report 3 Start trip test 2 Measurements 1 Display currents 2 Display peak factors 3 History 1 Trip History display 2 Events display 3 Statistics 1 Display contact wear 2 Display total no prot trips 3 Display no manual oper 4 Display no prot oper 5 Display no trip failures 6 Display no trip tests ...

Page 36: ... 2 Display plant config 3 Display CB TAG Name 4 Display User Data 2 Display mains frequency 3 Local bus unit 1 Local bus unit presence 2 Release 1 configuration 3 Release 2 configuration 4 Release 3 configuration 5 Release 4 configuration 6 Release 6 configuration 7 Release 7 configuration 8 Release 8 configuration 1 Type of signal source Display custom type 2 Display source configuration 3 Releas...

Page 37: ... procedure described in the following table A brief description of the various tests will be given below 1 Startup time protection S 0 1 Time 1 5 s step 0 01 s 2 Startup time protection S2 0 1 Time 1 5 s step 0 01 s 3 Startup time protection G 0 1 Time 1 5 s step 0 01 s 4 Startup time protection Gext 0 1 Time 1 5 s step 0 01 s 5 Startup time protection D 0 1 Time 1 5 s step 0 01 s 6 Startup curren...

Page 38: ...tion in particular it offers the possibility of selecting the current value in a range between 0 00 and 16 00 In and of selecting the phases involved in the test L1 L2 L3 Ne Gext The release trip time will depend on the settings of the protections on the display the PR010 T unit will show the trip time and the result of the test OK FAILED At the end of the test it is asked whether to record a test...

Page 39: ...y Under the history menu is the display of the history for the openings of the protection tripped the events and some statistical information on the openings of the release For example to display the history of the openings trip history the following selections must be made Key to be pressed Item selected 1 Operation mode x PR121 P 2 Measurements 1 Currents ENTER Key to be pressed Item selected 1 ...

Page 40: ...e main menu selecting enters the screen that displays the configuration parameters of the neutral protection and the following screen appears Pressing the ENTER key launches editing mode the cursor starts blinking the buttons and are used to position the cursor on the desired parameter and the buttons and to change the value of the parameters in the allowed range Key to be pressed Item selected 1 ...

Page 41: ...lecting Release x the configuration parameters of release x on the local bus unit are read set for example selecting The setting of the activation signal of release no 3 is displayed pressing the ENTER key launches editing mode the cursor starts blinking the setting of the activation signal is changed using the keys and If Custom is selected when ENTER is pressed the current setting is displayed f...

Page 42: ...OR logic applied to the selected elements and the minimum release activation time 13 6 2 Parameters The protection parameters are divided into 1 L protection 2 S protection 3 I protection 4 G protection For example selecting enters the screen that displays the parameters of protection L and the following screen appears Pressing the ENTER key launches editing mode the cursor starts blinking the but...

Page 43: ...d passes to the display of the next previous screen 13 8 Status On this menu it is possible to view any signals of an error in configuration wiring of the protection unit and of the circuit breaker In particular one or more of the following messages may be displayed 1 No alarm 2 L Prealarm 3 T Prealarm 4 L1 Sensor error 5 L2 Sensor error 6 L3 Sensor error 7 Ne Sensor error Key to be pressed Item s...

Page 44: ...sensor error 9 TC disconnected 10 Rating Plug error 11 Installation error 12 Device error 13 Invalid Date 14 Configuration error 15 CB status error Refer to the release user manual for the solution of the errors indicated 14 SACE PR122 P protection release ...

Page 45: ... Display voltages note 2 4 POWERS 1 Display active power 2 Display reactive power 3 Display apparent power 5 Display energies 6 Display power factor 7 Display measured frequency 8 Reset energies counters 9 Reset measurement history 3 History 1 Display trip history 2 Display events 3 Statistics 1 Display contact wear 2 Display total no prot trips 3 Display total no prot trips 4 Display no manual op...

Page 46: ...presence 3 Positive power direction 2 Communication note 3 1 Operation mode 2 Communication parameters 3 Signalling module note 4 1 Release 1 configuration 1 Type of signal source Display custom type 2 Display source configuration 2 Release 2 configuration 3 Release 3 configuration 4 Release 4 configuration 5 Input signalling module configuration 8 Local bus unit 1 Local bus unit presence 2 Releas...

Page 47: ...on G parameters note 6 5 Protection Ext G parameters note 6 6 Protection U parameters 7 Protection T parameters 8 Protection LC1 parameters 9 Protection LC2 parameters 10 Protection Iw parameters 11 Protection Rc parameters note 1 12 Protection MCR parameters 13 Protection UV parameters note 2 14 Protection OV parameters note 2 15 Protection RV parameters note 2 16 Protection RP parameters note 2 ...

Page 48: ...rotection unit in particular 1 Automatic test 2 Manual test 3 Trip test 4 Sign mod autotest 5 Force output S ZS 6 Force output G ZS 7 Release output ZS 8 Rc Test For example to perform the automatic test it is necessary to follow the procedure described in the following table 1 Startup time protection S 0 1 s Time 1 5 s step 0 01 s 2 Startup time protection S2 0 1 s Time 1 5 s step 0 01 s 3 Startu...

Page 49: ...equence of 13 different tests will be performed at the currents voltages phase shift and phases indicated in the following table For example test n 5 is performed with IL 0 3 In Test N Phase Value L1 L2 L3 1 u u u 0 3 In 2 u u u 3 0 In 3 u u u 5 0 In 4 u u u 10 0 In 5 u u u 15 0 In 6 u 0 3 In 7 u 3 0 In Test N Phase Amplitude Phase shift L1 L2 L3 V12 V23 V31 I In V Un Φ 1 u u u u u u 3 0 1 0 30 2 ...

Page 50: ...will show the trip time and the result of the test OK FAILED At the end of the test it is asked whether to record a test report which may later be downloaded on a PC 14 3 3 Trip test With this test it is possible to send a command to turn off the circuit breaker thus checking the functionality of the protection opening system The trip test command is accepted by the protection unit only if the cir...

Page 51: ...history For example to display the current measurements the following selections must be made 14 5 History Under the HISTORY menu is the display of the history for the openings of the protection tripped the events and some statistical information on the openings of the release For example to display the history of the openings trip history the following selections must be made Key to be pressed It...

Page 52: ...odules 8 Local bus unit 9 Data logger 10 System For example starting from the main menu selecting enters the screen that displays the configuration parameters of the neutral protection and the following screen appears Pressing the ENTER key launches editing mode the cursor starts blinking using the keys and the cursor is positioned on the desired parameter and the keys and are used to modify the v...

Page 53: ... bus Selecting Release x the configuration parameters of release x on the local bus unit are read set for example selecting The setting of the activation signal of release no 3 is displayed pressing the ENTER key launches editing mode the cursor starts blinking the setting of the activation signal is changed using the keys and If Custom is selected when ENTER is pressed the current setting is disp...

Page 54: ...tive screens up to 8 elements may be activated for each block On the last screen of each block it is possible to define the AND OR logic applied to the selected elements and the minimum release activation time 14 6 3 Parameters The protection parameters are divided into 1 L prot 2 S prot 3 I prot 4 G prot 5 Ext G prot 6 U prot 7 T prot 8 LC1 prot 9 LC2 prot 10 Iw prot 11 RC prot 12 MCR prot 13 UV ...

Page 55: ...menu it is possible to view some information on the protection unit and the circuit breaker The menu is divided into 1 Protection unit 2 Circuit breaker For example starting from the main menu selecting enters the screen that displays information on the circuit breaker Pressing the keys and passes to the display of the next previous screen L prot t k i2 Threshold x xx In Time x xx s Thermal mem ON...

Page 56: ...re of the following messages may be displayed 1 No alarm 2 L Prealarm 3 T Prealarm 4 L1 Sensor error 5 L2 Sensor error 6 L3 Sensor error 7 Ne Sensor error 8 Gext sensor error 9 TC disconnected 10 Rating Plug error 11 Installation error 12 Device error 13 Invalid Date 14 Configuration error 15 CB status error Refer to the release user manual for the solution of the errors indicated 15 SACE PR123 P ...

Page 57: ...OWERS 1 Display active power 2 Display reactive power 3 Display apparent power 5 Display energies 6 Display power factor 7 Display measured frequency 8 Reset energies counters 9 Reset measurement history 3 History 1 Display trip history 2 Display events 3 Statistics 1 Display contact wear 2 Display total no prot trips 3 Display total no prot trips 4 Display no manual operations 5 Display no prot o...

Page 58: ... on L Bus DI 7 Enable disable harmonic distortion alarm 8 Modules 1 Measuring 1 Voltage transformer parameters 2 Neutral voltage presence 3 Positive power direction 4 Warnings 1 Phase sequence configuration 2 Power factor configuration 2 Communication note 3 1 Operation mode 2 Communication parameters 3 Signalling module note 4 1 Release 1 configuration 1 Type of signal source Display custom type ...

Page 59: ...S parameters 3 Protection S2 parameters 4 Protection D parameters 5 Protection I parameters 6 Protection G parameters note 5 7 Protection Ext G parameters note 5 8 Protection U parameters 9 Protection T parameters 10 Protection LC1 parameters 11 Protection LC2 parameters 12 Protection Iw parameters 13 Protection Rc parameters note 1 14 Protection MCR parameters 15 Protection UV parameters 16 Prote...

Page 60: ...various menus is given below 15 3 Test By means of the PR010 T unit it is possible to perform some tests on the protection unit in particular 1 Automatic test 2 Manual test 3 Trip test 4 Sign mod autotest 5 Force output S ZS 6 Force output G ZS NOTES 1 Only for performing LSIG and presence of residual current in the external toroide 2 Only if measuring module present 3 Only if communication module...

Page 61: ...l be performed at the currents voltages phase shift and phases indicated in the following table For example test n 5 is performed with IL1 0 3 In IL2 IL3 0 In V12 V23 V31 1 Un Key to be pressed Item selected 1 Operation mode x PR123 P 1 Test 1 Automatic test ENTER Test N Phase Amplitude Phase shift Φ L1 L2 L3 V12 V23 V31 I In V Un 1 u u u u u u 3 0 1 30 2 u u u u u u 5 0 3 u u u u u u 10 4 u u u u...

Page 62: ... trip time and the result of the test OK FAILED At the end of the test it is asked whether to record a test report which may later be downloaded on a PC 15 3 3 Trip test With this test it is possible to send a command to turn off the circuit breaker thus checking the functionality of the protection opening system The trip test command is accepted by the protection unit only if the circuit breaker ...

Page 63: ...history For example to display the current measurements the following selections must be made 15 5 History Under the history menu is the display of the history for the openings of the protection tripped the events and some statistical information on the openings of the release For example to display the history of the openings trip history the following selections must be made Key to be pressed It...

Page 64: ...n 8 Modules 9 Local bus unit 10 Data logger 11 System For example starting from the main menu selecting enters the screen that displays the configuration parameters of the neutral protection and the following screen appears Pressing the ENTER key launches editing mode the cursor starts blinking using the keys and the cursor is positioned on the desired parameter and the keys and are used to modify...

Page 65: ...l bus Selecting Release x the configuration parameters of release x on the local bus unit are read set for example selecting The setting of the activation signal of release no 3 is displayed pressing the ENTER key launches editing mode the cursor starts blinking the setting of the activation signal is changed using the keys and If Custom is selected when ENTER is pressed the current setting is dis...

Page 66: ...en of each block it is possible to define the AND OR logic applied to the selected elements and the minimum release activation time 15 6 2 Parameters The PR123 P protection unit has two alternative parameter sets Set A and Set B the parameter reading programming menu contemplates the choice of the set of parameters to be displayed edited 1 Set A 2 Set B After having selected the test on which to o...

Page 67: ...lue of the parameters in the allowed range 15 7 Information On this menu it is possible to view some information on the protection unit and the circuit breaker The menu is divided into 1 Protection unit 2 Circuit breaker For example starting from the main menu selecting Key to be pressed Item selected 1 Operation mode x PR123 P 4 Config Parameters 2 Parameters 1 Set A 1 Protection L ENTER L prot t...

Page 68: ...of the circuit breaker In particular one or more of the following messages may be displayed 1 No alarm 2 L Prealarm 3 T Prealarm 4 L1 Sensor error 5 L2 Sensor error 6 L3 Sensor error 7 Ne Sensor error 8 Gext sensor error 9 TC disconnected 10 Rating Plug error 11 Installation error 12 Device error 13 Invalid Date 14 Configuration error 15 CB status error Refer to the release manual for the solution...