11.2 Indications on operation
• The SACE PR010/T unit can be used with all SACE PR113/P and SACE PR113/PD protec-
tion releases.
• The SACE PR113/PD releases must be connected to the auxiliary power supply for use with
the SACE PR010/T unit.
• The tests must be carried out with the circuit breaker off, no voltage to the busbar (V=0)
(where the VTs are installed to measure the SACE PR113/P and SACE PR113/PD release
voltage) and the auxiliary power supply enabled.
WARNING
Connect the test wire provided (between the SACE PR010/T and the SACE
PR113) the right way round (see the adhesive labels on the connectors).
Example of an automatic test application on the PR113 release.
NOTE:
the data on the CB and protection, on the current rating of the CTs and
on the neutral setting are automatically identified by the PR010/T.
In this example, all the protection functions implemented by the SACE PR113/P and SACE
PR113/PD release are tested automatically:
1. Operat
ion
mo
de
2. Sele
ct DUT
(PR1
13)
3. Program
min
g
1. Change DUT
config./
parameters
1. DUT config.
Change DUT configuration parameters
2. DUT param.
1. Protection
parameters
Change DUT protection
parameters
2. Other
parameters
Change other parameters
2. Download def.
parameters
Download
3. Def. parameters
in PR010/T
1. For test
1. DUT config.
Change DUT configuration
2. DUT param.
1. Protection
parameters
Change
protect. par.
2. Operative
1. DUT config.
Change DUT configuration
2. DUT param.
1. Protection
parameters
Change
parameters
2. Other
parameters
Change
other
parameters
1. From the main menu select
1
(Operation mode)
2. Select the PR113 unit with
x
(PR113)
3. Select the type of activity with
1
(Test)
4. Select the type of test with
1
(Protections)
5. Select the test mode with
1
(Automatic)
6. Pressing ENTER enables a simulation of the failure for each protection function.
1° 2° 3° 4°
5°
6°
7°
8°
9°