6.6
Applicable standards
The SACE PR010/T test unit bears the CE quality mark and fully complies with all major
international standards on electromagnetic compatibility (EMC).
6.7
Error messages and troubleshooting table
Emissions:
IEN55022 class B
Electrostatic discharge:
IEC/EN 61000-4-2
Radiated immunity:
IEC/EN 61000-4-3
Conducted immunity:
IEC/EN 61000-4-6 (1kV)
UPDATE ERROR
“SW updating failed”
“Press ESC to restart”
This message indicates a software updating
error. To rectify, repeat the operation, after first
checking the PC-PR010/T connection and the
name of the loaded file.
COMMUNICATION ERROR
"Communication error"
"Press ESC to return"
This message indicates that the SACE PR010/
T's internal bus is unable to establish a
connection with the device under test.
INVALID DIGITAL VOLTAGE
"DUT internal voltage not valid"
"Press ESC to return"
This message indicates an internal DUT
voltage reading that is outside the accepted
range.
INVALID PROGRAM
"Program failed"
"Press ENTER for recovery"
If this message is displayed when the SACE
PR010/T test unit is powered up, it means that
the program stored in the SACE PR010/T's
memory is incorrect due to the failure of a
previous software updating sequence.
In this situation, the SACE PR010/T test unit
cannot work and must therefore be reloaded
with the updated software.