ABB | SACE Emax 2
Accessories | 2 - Rating Plug
49 | © 2019 ABB | 1SDH001000R0002 - ECN000109166 - Rev. D
Mechanical accessories
Electrical and mechanical accessories for E2.2-E4.2-E6.2:
Type of accessory
Accessory
Circuit-breakers
Switch-disconnectors
Electrical signalling
AUX 4Q
S
R
AUX 6Q
R
R
AUX 15Q
(5)
R
R
Ekip AUP
(1)
R
R
Ekip RTC
R
R
S51
S
-
S51/2
(6)
R
-
S33 M/2
R
R
Electrical control
YO
(4)
- YC
R
R
YO2
(4)
- YC2
R
R
YU
(2)(4)
R
R
YU2
(2)(4)
R
R
M
R
R
YR
R
-
Security mechanical
KLC - PLC
R
R
KLP - PLP
(1)
R
R
SL
(1)
S
S
DLR
(1)
R
R
DLP
(1)
R
R
DLC
(5)
R
R
Anti-insertion lock
S
S
MOC
R
R
FAIL SAFE
(3)
R
R
Protection mechanical
PBC
R
R
IP54
R
R
Interlocks
MI
(5)
R
R
S: Standard. R: on request.
(1)
For withdrawable version only.
(2)
Incompatible with FAIL SAFE. Can be ordered for UL on request
(3)
Incompatible with YU; standard for UL version.
(4)
A maximum of two accessories are available for YO and YU.
(5)
Not available for withdrawable circuit-breakers with lateral fastening.
(6)
Incompatible with YR
2 - Rating Plug
Description
The
Rating Plug
, supplied with Ekip Touch, establishes the rated current In required by the measuring range
and sets the current protections (with reference to In).
It is installed on a dedicated front connector and is accessible to the user for inspections or replacement
following a change of model/size.
For further details about the available models, operations and reference documents, consult document