76 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
Ekip Touch protection trip unit | 10 - Measuring Pro protections
UV Protection
U8
t
t8
v
UV
Path
Main page - Menu - Advanced
Function
UV protection trips when the phase-to-phase voltage drops below the set threshold.
If at least one line-to-line voltage drops below the activation threshold, the protection trips within a fixed time
set by the user.
Parameters
Here is a list of the available parameters:
Parameter
Description
Enable
To activate/deactivate the protection.
Threshold U8
It defines the voltage value below which the protection is activated (with
reference to the figure above, the threshold is the part of the curve parallel to
the y-axis).
It is represented both as an absolute value (Volts) and a relative value (Un,
nominal value defined on the trip unit).
Time t8
The delay time between the exceeding of the U8 threshold and the sending of
the opening command (with reference to the figure above, the threshold is the
part of the curve parallel to the x-axis).
UV protection has
StartUp enable
, see page 71.
Via Ekip Connect it is also possible to access the
blocking functions
, see page 72.
OV Protection
U9
t
t9
V
OV
Path
Main page - Menu - Advanced
Function
OV protection trips when the phase-to-phase voltage rises above the set threshold.
If at least one line-to-line voltage rises above the activation threshold, the protection trips within a fixed time
set by the user.
Parameters
Here is a list of the available parameters:
Parameter
Description
Enable
To activate/deactivate the protection.
Threshold U9
It defines the voltage value above which the protection is activated (with
reference to the figure above, the threshold is the part of the curve parallel to
the y-axis).
It is represented both as an absolute value (Volts) and a relative value (Un,
nominal value defined on the trip unit).
Time t9
The delay time between the exceeding of the U9 threshold and the sending of
the opening command (with reference to the figure above, the threshold is the
part of the curve parallel to the x-axis).
OV protection has
StartUp enable
, see page 71.
Via Ekip Connect it is also possible to access the
blocking functions
, see page 72.
Summary of Contents for SACE Emax E1.2
Page 2: ...ABB SACE Emax 2 2 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Page 8: ...VI 2017 ABB SACE Emax 2 1SDH001330R0002 ECN000058721 Rev A ...
Page 9: ...ABB SACE Emax 2 3 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Page 310: ...ABB SACE Emax 2 304 2017 ABB 1SDH001330R0002 ECN000058721 Rev A Service 1 Power Care ...