50 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
Ekip Touch protection trip unit | 6 - Menu
Continued from the previous page
Settings
Options
Dual Set
• Enable: it opens the
Modify Parameters
page, to enable/disable dual configuration
of the protections.
• Default Set: available with Dual Set enabled, it opens the
Modify Parameters
page,
to set the default configuration.
System
• Date: it opens the
Modify Parameters
page, to set the date.
• Time: it opens the
Modify Parameters
page, to set the time
• Language: it opens the
Modify Parameters
page, to set the language.
• New Password: it opens the page for insertion of the password.
View
• TFT orientation: it opens the
Modify Parameters
page to set the orientation of
the
Alarm List
and
Measuring instruments
pages, and with a summary of the
measurements accessible from the
Histograms
page.
• Ammeter Phase: it opens the
Modify Parameters
page to set the current the
measurement of which is to be displayed in the
Measuring instruments
page.
• Voltmeter phase: it opens the
Modify Parameters
page to set the phase-to-phase
voltage the measurement of which is to be displayed in the
Measuring instruments
page.
• Clients page: it opens the
Modify Parameters
page, to enable the
Info
(4)
page.
Functions
•
YO Command
: opens the list of parameters that can be set for programming the coil
opening command.
•
YC Command
: opens the list of parameters that can be set for programming the coil
closing command.
Maintenance
• Signals: it opens the
Modify Parameters
page, in order to enable/disable the
maintenance required signal, after a year from the last maintenance, or with contact
wear of at least 20 % and an increase of 10 % compared to the last maintenance.
(1)
The options in the Modules submenu change according to the electronic accessories connected.
(2)
Function available with the trip unit energized with auxiliary voltage.
(3)
Setting available with Hi-Touch and G Hi-Touch trip units.
(4)
If enabled, the Info page can be accessed by pressing the iTEST key until it appears; it displays five lines of
twenty characters each containing alphanumeric data that the customer can insert through the Ekip Connect
software (see the chapter "16 - Other accessories", and the paragraph "Ekip Connect software" on page 245).
Test Menu
This menu allows you to access the commands in order to perform the tests.
The following table shows the submenus and the commands associated to the menus
Test
, up to Level
3 (if present). The options corresponding to commands are underlined, to distinguish them from those
corresponding to submenus.
Test
Option
Rc Test
(1)
Test protection Rc.
Auto Test
It performs a test on the display and LEDs of the interface.
Trip Test
it enables the opening command.
Test CB
• Close CB: it commands the closing of the circuit-breaker.
• Open CB: it commands the opening of the circuit-breaker.
Ekip Signalling 2K
(2)
• Auto Test
Ekip Signalling 4K
(2)
• Auto Test
Zone selectivity (68)
•
S Protection
: opens a list of the test commands of the Zone Selectivity
function for S protection.
•
G Protection
: it opens a list of the test commands of the Zone Selectivity
function for G protection.
(1)
Test available with Rating Plug Rc and Ekip Measuring Pro modules, and toroid Rc (see Settings - Circuit
Breaker - Earth protection menu).
(2)
These menus are available if the relevant modules are connected.
Summary of Contents for SACE Emax E1.2
Page 2: ...ABB SACE Emax 2 2 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Page 8: ...VI 2017 ABB SACE Emax 2 1SDH001330R0002 ECN000058721 Rev A ...
Page 9: ...ABB SACE Emax 2 3 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Page 310: ...ABB SACE Emax 2 304 2017 ABB 1SDH001330R0002 ECN000058721 Rev A Service 1 Power Care ...