ABB | SACE Emax 2
Electrical accessories | 2 - Electrical signalling accessories
259 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
S33 M/2: springs charged
signalling contact
The S33 M/2 contact signals the state of the closing springs of the circuit-breaker control (charged or
discharged).
It is available in two types:
• standard contact
• contact for digital signals
NOTE:
the S33_M/2 contact is always included in the gearmotor for automatic charging of
the springs in the standard version. The version for digital signals must be requested with the
order for the motor.
38
36
35
S33
S33 M/2 for E1.2
38
36
35
S33
S33 M/2 for E2.2 - E4.2 - E6.2
The following table provides information on the electrical characteristics:
Characteristics
Standard
Digital signals
Breaking
capacity
DC
24V
-
0.1 A
125V
0.5A @ 0ms / 0.3A @ 10ms
-
250V
0.3A @ 0ms / 0.15A @ 10ms
-
AC
250V
3A cos
φ
0.3
-
5A cos
φ
0.7
-
5A cos
φ
1
-
400V
3A cos
φ
1
-
2A cos
φ
0.7
-
1A cos
φ
0.3
-
Minimum load
100mA @ 24V
1mA @ 5V
S33/M2: Connections
Further information is available on page 174, or on the website http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/,
in particular for E1.2 in the kit sheet
and for E2.2-E4.2-E6.2 in the kit sheet
Summary of Contents for SACE Emax E1.2
Page 2: ...ABB SACE Emax 2 2 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Page 8: ...VI 2017 ABB SACE Emax 2 1SDH001330R0002 ECN000058721 Rev A ...
Page 9: ...ABB SACE Emax 2 3 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Page 310: ...ABB SACE Emax 2 304 2017 ABB 1SDH001330R0002 ECN000058721 Rev A Service 1 Power Care ...