ABB | SACE Emax 2
256 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
Electrical accessories | 2 - Electrical signalling accessories
AUP: auxiliary position contacts
The AUP contacts are intended for circuit-breakers in withdrawable version.
They electrically signal the position of a moving part (inserted/test/withdrawn) in relation to the fixed part in
which they are inserted.
These are "switching" contacts and are available in the following configurations:
Up to a maximum of six contacts for E1.2:
• six standard contacts
• six digital signals
Up to a maximum of ten contacts for E2.2-E4.2-E6.2:
• five standard contacts
• five digital signals
• five additional standard contacts
• five additional digital signals
AUP for E1.2
AUP for E2.2 - E4.2 - E6.2
The following table provides information on the electrical characteristics:
Characteristics
Standard
Digital signals
Breaking
capacity
DC
24V
-
0.1 A
125V
0.5A @ 0ms / 0.3A @ 10ms
-
250V
0.3A @ 0ms / 0.15A @ 10ms
-
AC
250V
3A cos
φ
0.3
-
5A cos
φ
0.7
-
5A cos
φ
1
-
400V
3A cos
φ
1
-
2A cos
φ
0.7
-
1A cos
φ
0.3
-
Minimum load
100mA @ 24V
1mA @ 5V
AUP: Connections
Further information is available on page 174, or on the website http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/,
in particular for E1.2 in the kit sheet
and for E2.2-E4.2-E6.2 in the kit sheet
Summary of Contents for SACE Emax E1.2
Page 2: ...ABB SACE Emax 2 2 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Page 8: ...VI 2017 ABB SACE Emax 2 1SDH001330R0002 ECN000058721 Rev A ...
Page 9: ...ABB SACE Emax 2 3 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Page 310: ...ABB SACE Emax 2 304 2017 ABB 1SDH001330R0002 ECN000058721 Rev A Service 1 Power Care ...