2105552MNAE | RMC-100 |
129
Figure 7-2: AI 1 set to voltage mode
4.
Turn on the calibrator.
5.
Click the
Calibrate
icon on the PCCU toolbar. The calibration Checks screen displays with a
request to take an application out of hold (
). This example shows the request for
AGA3-2.
IMPORTANT NOTE:
The calibration mode automatically places active measurement applications
on hold. This is not required for I/O calibration. The calibration navigation tree in
shows
four AGA3 applications. The checkmark indicates that they are all in Hold mode. Pop-ups display to
remove applications from hold. Accept them all. These requests display one at a time until the last
application is out of hold.