Binary inputs of slot X120 are available with configuration B.
Table 31:
Binary input terminals X120-1...6
Terminal
Description
X120-1
BI1, +
X120-2
BI1, -
X120-3
BI2, +
X120-2
BI2, -
X120-4
BI3, +
X120-2
BI3, -
X120-5
BI4, +
X120-6
BI4, -
Binary inputs of slot X130 are available with configuration A and optional for
configuration B.
Table 32:
Binary input terminals X130-1...9
Terminal
Description
X130-1
BI1, +
X130-2
BI1, -
X130-2
BI2, -
X130-3
BI2, +
X130-4
BI3, +
X130-5
BI3, -
X130-5
BI4, -
X130-6
BI4, +
X130-7
BI5, +
X130-8
BI5, -
X130-8
BI6, -
X130-9
BI6, +
5.2
Outputs
5.2.1
Outputs for tripping and controlling
Output contacts PO1, PO2, PO3 and PO4 are heavy-duty trip contacts capable of
controlling most circuit breakers. On delivery from the factory, the trip signals
from all the protection stages are routed to PO3 and PO4.
Section 5
1MRS757054 A
IED physical connections
66
REU615
Application Manual