19.3
Energizing inputs
Table 539:
TRM — Energizing quantities, rated values and limits for transformer inputs
Description
Value
Frequency
Rated frequency f
r
50 or 60 Hz
Operating range
f
r
± 10%
Current inputs
Rated current I
r
0.1 or 0.5 A
1)
1 or 5 A
2)
Operating range
0 – 50 A
0 – 500 A
Thermal withstand
100 A for 1 s
500 A for 1 s
*)
20 A for 10 s
100 A for 10 s
8 A for 1 min
40 A for 1 min
4 A continuously
20 A continuously
Dynamic withstand
250 A one half wave
1250 A one half wave
Burden
< 1 mVA at I
r
= 0.1 A
< 10 mVA at I
r
= 1 A
< 20 mVA at I
r
= 0.5 A
< 200 mVA at I
r
= 5 A
*)
max. 350 A for 1 s when COMBITEST test switch is included.
Voltage inputs
**)
Rated voltage U
r
100 or 220 V
Operating range
0 – 420 V
Thermal withstand
450 V for 10 s
420 V continuously
Burden
< 50 mVA at 100 V
< 200 mVA at 220 V
**)
all values for individual voltage inputs
Note! All current and voltage data are specified as RMS values at rated frequency
1) Residual current
2) Phase currents or residual current
19.4
Binary inputs
Table 540:
Binary inputs
Description
Value
Operating range
Maximum input voltage 300 V DC
Rated voltage
24...250 V DC
Current drain
1.6...1.8 mA
Power consumption/input
<0.38 W
Threshold voltage
15...221 V DC (parametrizable in the range in steps
of 1% of the rated voltage)
Section 19
1MRK 504 135-UEN A
Technical data
616
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...