Table 491:
CHNGLCK Output signals
Name
Type
Description
ACTIVE
BOOLEAN
Change lock active
OVERRIDE
BOOLEAN
Change lock override
17.5.5
Settings
The function does not have any parameters available in Local HMI or Protection and
Control IED Manager (PCM600)
17.5.6
Operation principle
The Change lock function (CHNGLCK) is configured using ACT.
The function, when activated, will still allow the following changes of the IED state
that does not involve reconfiguring of the IED:
•
Monitoring
•
Reading events
•
Resetting events
•
Reading disturbance data
•
Clear disturbances
•
Reset LEDs
•
Reset counters and other runtime component states
•
Control operations
•
Set system time
•
Enter and exit from test mode
•
Change of active setting group
The binary input signal LOCK controlling the function is defined in ACT or SMT:
Binary input
Function
1
Activated
0
Deactivated
17.6
IED identifiers TERMINALID
17.6.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
IED identifiers
TERMINALID
-
-
Section 17
1MRK 504 135-UEN A
Basic IED functions
578
Technical manual