The input of this GOOSE block must be linked in SMT by means of
a cross to receive the binary values.
The implementation for IEC61850 quality data handling is restricted
to a simple level. If quality data validity is GOOD then the OUTxVAL
output will be HIGH. If quality data validity is INVALID,
QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA then
the OUTxVAL output will be LOW.
16.5
GOOSE VCTR configuration for send and receive
GOOSEVCTRCONF
16.5.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
GOOSE VCTR configuration for send
and receive
GOOSEVCTRC
ONF
-
-
16.5.2
Functionality
GOOSEVCTRCONF function is used to control the rate (in seconds) at which voltage
control information from TR8ATCC is transmitted/received to/from other IEDs via
GOOSE communication. GOOSEVCTRCONF function is visible in PST.
The following voltage control information can be sent from TR8ATCC via GOOSE
communication:
•
BusV
•
LoadAIm
•
LoadARe
•
PosRel
•
SetV
•
VCTRStatus
•
X2
1MRK 504 135-UEN A
Section 16
Station communication
541
Technical manual