Section 15
Metering
15.1
Pulse counter PCGGIO
15.1.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Pulse counter
PCGGIO
S00947 V1 EN
-
15.1.2
Functionality
Pulse counter (PCGGIO) function counts externally generated binary pulses, for
instance pulses coming from an external energy meter, for calculation of energy
consumption values. The pulses are captured by the BIO (binary input/output) module
and then read by the PCGGIO function. A scaled service value is available over the
station bus.
15.1.3
Function block
IEC09000335-2-en.vsd
PCGGIO
BLOCK
READ_VAL
BI_PULSE*
RS_CNT
INVALID
RESTART
BLOCKED
NEW_VAL
SCAL_VAL
IEC09000335 V2 EN
Figure 236:
PCGGIO function block
15.1.4
Signals
Table 431:
PCGGIO Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
READ_VAL
BOOLEAN
0
Initiates an additional pulse counter reading
BI_PULSE
BOOLEAN
0
Connect binary input channel for metering
RS_CNT
BOOLEAN
0
Resets pulse counter value