used to get information about the recordings. The disturbance report files may be
uploaded to PCM600 for further analysis using the disturbance handling tool.
14.4.2
Disturbance report DRPRDRE
14.4.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Disturbance report
DRPRDRE
-
-
14.4.2.2
Function block
DRPRDRE
DRPOFF
RECSTART
RECMADE
CLEARED
MEMUSED
IEC09000346-1-en.vsd
IEC09000346 V1 EN
Figure 200:
DRPRDRE function block
14.4.2.3
Signals
Table 368:
DRPRDRE Output signals
Name
Type
Description
DRPOFF
BOOLEAN
Disturbance report function turned off
RECSTART
BOOLEAN
Disturbance recording started
RECMADE
BOOLEAN
Disturbance recording made
CLEARED
BOOLEAN
All disturbances in the disturbance report cleared
MEMUSED
BOOLEAN
More than 80% of memory used
14.4.2.4
Settings
Table 369:
DRPRDRE Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off/On
PreFaultRecT
0.05 - 9.90
s
0.01
0.10
Pre-fault recording time
PostFaultRecT
0.1 - 10.0
s
0.1
0.5
Post-fault recording time
TimeLimit
0.5 - 10.0
s
0.1
1.0
Fault recording time limit
PostRetrig
Off
On
-
-
Off
Post-fault retrig enabled (On) or not (Off)
Table continues on next page
Section 14
1MRK 504 135-UEN A
Monitoring
446
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...