Signals
Table 286:
PULSETIMER Input signals
Name
Type
Default
Description
INPUT
BOOLEAN
0
Input signal
Table 287:
PULSETIMER Output signals
Name
Type
Description
OUT
BOOLEAN
Output signal
Settings
Table 288:
PULSETIMER Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
t
0.000 - 90000.000
s
0.001
0.010
Pulse time length
13.3.1.5
Controllable gate function block GATE
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Controllable gate function block
GATE
-
-
Functionality
The GATE function block is used for controlling if a signal should pass from the input
to the output or not, depending on setting.
Function block
GATE
INPUT
OUT
IEC09000295-1-en.vsd
IEC09000295 V1 EN
Figure 170:
GATE function block
Signals
Table 289:
GATE Input signals
Name
Type
Default
Description
INPUT
BOOLEAN
0
Input signal
Section 13
1MRK 504 135-UEN A
Logic
382
Technical manual