Name
Type
Description
P11
BOOLEAN
Selector switch position 11
P12
BOOLEAN
Selector switch position 12
P13
BOOLEAN
Selector switch position 13
P14
BOOLEAN
Selector switch position 14
P15
BOOLEAN
Selector switch position 15
P16
BOOLEAN
Selector switch position 16
P17
BOOLEAN
Selector switch position 17
P18
BOOLEAN
Selector switch position 18
P19
BOOLEAN
Selector switch position 19
P20
BOOLEAN
Selector switch position 20
P21
BOOLEAN
Selector switch position 21
P22
BOOLEAN
Selector switch position 22
P23
BOOLEAN
Selector switch position 23
P24
BOOLEAN
Selector switch position 24
P25
BOOLEAN
Selector switch position 25
P26
BOOLEAN
Selector switch position 26
P27
BOOLEAN
Selector switch position 27
P28
BOOLEAN
Selector switch position 28
P29
BOOLEAN
Selector switch position 29
P30
BOOLEAN
Selector switch position 30
P31
BOOLEAN
Selector switch position 31
P32
BOOLEAN
Selector switch position 32
SWPOSN
INTEGER
Switch position as integer value
12.4.5
Settings
Table 247:
SLGGIO Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off/On
NrPos
2 - 32
-
1
32
Number of positions in the switch
OutType
Pulsed
Steady
-
-
Steady
Output type, steady or pulse
tPulse
0.000 - 60.000
s
0.001
0.200
Operate pulse duration
tDelay
0.000 - 60000.000
s
0.010
0.000
Output time delay
StopAtExtremes
Disabled
Enabled
-
-
Disabled
Stop when min or max position is reached
Section 12
1MRK 504 135-UEN A
Control
354
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...