8.3.2
Functionality
The Instantaneous residual overcurrent protection EFPIOC has a low transient
overreach and short tripping times to allow use for instantaneous earth-fault
protection, with the reach limited to less than typical eighty percent of the transformer
impedance at minimum source impedance. EFPIOC can be configured to measure the
residual current from the three-phase current inputs or the current from a separate
current input. EFPIOC can be blocked by activating the input BLOCK.
8.3.3
Function block
EFPIOC
I3P*
BLOCK
TRIP
IEC08000003 V1 EN
Figure 68:
EFPIOC function block
8.3.4
Signals
Table 79:
EFPIOC Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Three phase group signal for current inputs
BLOCK
BOOLEAN
0
Block of function
Table 80:
EFPIOC Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip signal
8.3.5
Settings
Table 81:
EFPIOC Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
IN>>
1 - 2500
%IB
1
200
Operate residual current level in % of
IBase
Table 82:
EFPIOC Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
1MRK 504 135-UEN A
Section 8
Current protection
153
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...