Figure 66:
Simplified logic diagram for OC4PTOC
8.2.8
Second harmonic blocking element
A harmonic restrain of the Four step overcurrent protection function OC4PTOC can
be chosen. If the ratio of the 2nd harmonic component in relation to the fundamental
frequency component in the residual current exceeds the preset level defined by
parameter
2ndHarmStab
setting, any of the four overcurrent stages can be selectively
blocked by parameter
HarmRestrainx
setting. When 2nd harmonic restraint feature is
active, the OC4PTOC function output signal 2NDHARMD will be set to logical value
one.
a
b
a>b
BLOCK
AND
I
OP
Extract second
harmonic current
component
Extract
fundamental
current component
X
2ndHarmStab
a
b
a>b
a
b
a>b
0.07*IBase
IEC13000014-1-en.vsd
2NDHARMD
2ndH_BLOCK_Int
IEC13000014 V1 EN
Figure 67:
Second harmonic blocking
1MRK 504 135-UEN A
Section 8
Current protection
151
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...