8.1.5
Settings
Table 68:
PHPIOC Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
IP>>
5 - 2500
%IB
1
200
Operate phase current level in % of IBase
Table 69:
PHPIOC Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
8.1.6
Monitored data
Table 70:
PHPIOC Monitored data
Name
Type
Values (Range)
Unit
Description
IL1
REAL
-
A
Current in phase L1
IL2
REAL
-
A
Current in phase L2
IL3
REAL
-
A
Current in phase L3
8.1.7
Operation principle
The sampled analogue phase currents are pre-processed in a discrete Fourier filter
(DFT) block. The RMS value of each phase current is derived from the fundamental
frequency components, as well as sampled values of each phase current. These phase
current values are fed to the instantaneous phase overcurrent protection 3-phase
output function PHPIOC. In a comparator the RMS values are compared to the set
operation current value of the function
(IP>>)
. If a phase current is larger than the set
operation current a signal from the comparator for this phase is set to true. This signal
will, without delay, activate the TRIP signal that is common for all three phases.
PHPIOC can be blocked from the binary input BLOCK.
8.1.8
Technical data
Table 71:
PHPIOC technical data
Function
Range or value
Accuracy
Operate current
(5-2500)% of lBase
±
1.0% of I
r
at I
£
I
r
±
1.0% of I at I > I
r
Reset ratio
> 95%
-
Operate time
20 ms typically at 0 to 2 x I
set
-
Table continues on next page
Section 8
1MRK 504 135-UEN A
Current protection
142
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...