input signal to the function. The function generates alarms based on the received
information.
13.2.3
Setting guidelines
GUID-DF6BEC98-F806-41CE-8C29-BEE9C88FC1FD v2
The parameters for Gas medium supervision SSIMG can be set via local HMI or
Protection and Control Manager PCM600.
Operation
: This is used to disable/enable the operation of gas medium supervision
i.e. Off/On.
PresAlmLimit
: This is used to set the limit for a pressure alarm condition in the
circuit breaker.
PresLOLimit
: This is used to set the limit for a pressure lockout condition in the
circuit breaker.
TempAlarmLimit
: This is used to set the limit for a temperature alarm condition in
the circuit breaker.
TempLOLimit
: This is used to set the limit for a temperature lockout condition in
the circuit breaker.
tPressureAlarm
: This is used to set the time delay for a pressure alarm indication,
given in s.
tPressureLO
: This is used to set the time delay for a pressure lockout indication,
given in s.
tTempAlarm
: This is used to set the time delay for a temperature alarm indication,
given in s.
tTempLockOut
: This is used to set the time delay for a temperature lockout
indication, given in s.
tResetPressAlm
: This is used for the pressure alarm indication to reset after a set
time delay in s.
tResetPressLO
: This is used for the pressure lockout indication to reset after a set
time delay in s.
tResetTempLO
: This is used for the temperature lockout indication to reset after a
set time delay in s.
tResetTempAlm
: This is used for the temperature alarm indication to reset after a set
time delay in s.
Section 13
1MRK 504 169-UEN A
Monitoring
278
Transformer protection RET650 2.2 IEC
Application manual
Summary of Contents for ret650
Page 1: ...RELION 650 SERIES Transformer protection RET650 Version 2 2 Application manual...
Page 2: ......
Page 28: ...22...
Page 38: ...32...
Page 42: ...36...
Page 80: ...74...
Page 168: ...162...
Page 174: ...168...
Page 250: ...244...
Page 346: ...340...
Page 366: ...360...
Page 390: ...384...
Page 391: ...385...