Section 6
1MAC309294-MB F
Condition monitoring functions
374
RER620
Technical Manual
6.1.7
Settings
Table 328: 52CM Non group settings
Parameter
Values (Range)
Unit Step
Default
Description
Operation
1=Enable
5=Disable
5=Disable
Operation Disable / Enable
Acc stop current
5.00...500.00
A
0.01
10.00
RMS current setting below which engy acm stops
Open alarm time
0...200
ms
1
40
Alarm level setting for open travel time in ms
Close alarm time
0...200
ms
1
40
Alarm level Setting for close travel time in ms
Opening time Cor
0...100
ms
1
10
Correction factor for open travel time in ms
Closing time Cor
0...100
ms
1
10
Correction factor for CB close travel time in ms
Spring charge time
0...60000
ms
10
1000
Setting of alarm for spring charging time of CB in ms
Counter initial Val A
0...9999
1
0
Phase A operation numbers counter initialization value
Counter initial Val B
0...9999
1
0
Phase B operation numbers counter initialization value
Counter initial Val C
0...9999
1
0
Phase C operation numbers counter initialization value
Alarm Op number
0...9999
1
200
Alarm limit for number of operations
Lockout Op number
0...9999
1
300
Lock out limit for number of operations
Current exponent
0.00...2.00
0.01
2.00
Current exponent setting for energy calculation
Difference Cor time
-10...10
ms
1
5
Corr. factor for time dif in aux. and main contacts open time
Alm Acc currents Pwr
0.00...20000.00
0.01
2500.00
Setting of alarm level for accumulated currents power
LO Acc currents Pwr
0.00...20000.00
0.01
2500.00
Lockout limit setting for accumulated currents power
Ini Acc currents Pwr A
0.00...20000.00
0.01
0.00
Phase A Initial value for accumulation energy (Iyt)
Ini Acc currents Pwr B
0.00...20000.00
0.01
0.00
Phase B Initial value for accumulation energy (Iyt)
Ini Acc currents Pwr C
0.00...20000.00
0.01
0.00
Phase C Initial value for accumulation energy (Iyt)
Directional Coef
-3.00...-0.50
0.01
-1.50
Directional coefficient for CB life calculation
Ini CB Rmn life A
0...9999
1
5000
Phase A Initial value for the CB remaining life
Ini CB Rmn life B
0...9999
1
5000
Phase B Initial value for the CB remaining life
Ini CB Rmn life C
0...9999
1
5000
Phase C Initial value for the CB remaining life
Rated Op current
100.00...5000.00
A
0.01
1000.00
Rated operating current of the breaker
Rated fault current
500.00...75000.00
A
0.01
5000.00
Rated fault current of the breaker
Op number rated
1...99999
1
10000
Number of operations possible at rated current
Op number fault
1...10000
1
1000
Number of operations possible at rated fault current
Life alarm level
0...99999
1
500
Alarm level for CB remaining life
Pressure alarm time
0...60000
ms
1
10
Time delay for gas pressure alarm in ms
Pres lockout time
0...60000
ms
10
10
Time delay for gas pressure lockout in ms
Inactive Alm days
0...9999
d
1
2000
Alarm limit value of the inactive days counter
Ini inactive days A
0...9999
d
1
0
Phase A Initial value of the inactive days counter
Ini inactive days B
0...9999
d
1
0
Phase B Initial value of the inactive days counter
Ini inactive days C
0...9999
d
1
0
Phase C Initial value of the inactive days counter
Inactive Alm hours
0...23
h
1
0
Alarm time of the inactive days counter in hours
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......