Loop Schemes can be setup as one-way or two-way systems. One-way systems allow the
tiepoint recloser close when voltage is lost on one side but not the other. This may be
necessary for situations where the one feeder cannot support additional load but can be
picked up by the other feeder. Two-way schemes are more common, and are set to pick up
load in either direction. For two-way schemes, there may be a need for an alternate
protection setting group change for proper coordination. This can be done automatically
based on programmed settings.
5.4.5.2
Five-Recloser Loop Control
The five-recloser system is similar to the three-recloser system except that a normally
closed Midpoint recloser divides the segments between the TiePoint recloser and each
Sectionalizing recloser.
Figure 185 shows the relative location of midpoint reclosers. The
Mid-point recloser differs from Sectionalizing and TiePoint reclosers in that it does not
initiate breaker operations (trip or close) based on phase voltages. Instead, it alters the
RER620's response to overcurrent conditions. Upon a loss of voltage (below dead bus
threshold voltage level) and after the programmed Dead bus time, the Midpoint RER620
will activate have two additional outputs, which include:
• Switch-on-to-fault (SWOTF)
• SET_GROUP_CHANGE
If the status of phases selected is dead, the SET_GROUP_CHANGE is activated if "En Set
Grp chg" setting is TRUE and SWOTF output is activated for time of SWOTF time setting
preventing the recloser from reclosing back into an anticipated fault for a back feed
condition (after the tie-point closes).
Time
Event or Conditon
t0
Permanent fault occurs between Sectionalizing and TiePoint reclosers.
t1
Sectionalizing recloser trips and locks out causing loss of voltage at the TiePoint recloser..
t2
TiePoint recloser declares phases dead, initiates loop control sequence and closes its
breaker.
t3
TiePoint recloser senses line fault, trips and locks out.
Permanent
Fault Initiates
Recloser B
Recloser B locks out
Recloser T
changes to ALT1
settings, Closes
then locks out on
one shot due to fault
2
t
0
t
t1
45 s - 3rd reclose and lockout
15 s - 2nd reclose
0.5 s - 1st reclose
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......