Section 5
1MAC309294-MB F
Control functions
338
RER620
Technical Manual
the Sectionalizing recloser, the Sectionalizing recloser will open after a program delay to
set up for the back feeding from the alternate source. This timer is set to expire prior to the
Midpoint and Tiepoint timers.
5.4.3.2
Midpoint Recloser
The Midpoint recloser also is normally closed. Unlike the Sectionalizing recloser,
however, it does not open in response to phase voltage loss. Instead, it supports loop
control by automatically altering the RER620 settings in accordance with changing
voltage conditions. Specifically, upon the expiration of it's under voltage timer, it will
switch to a new setting group to prepare for a back feed condition and for a period will go
into non-reclose mode. The reason for the nonreclose is that in the event the fault is
between the Sectionalizing unit and the Midpoint, it would be undesirable to have the
recloser sequence through multiple operations. Though the reclose blocked condition will
change to normal after a programmed amount of time, the control will stay in New Settings
Group until the loop scheme is reset.
5.4.3.3
Tiepoint Recloser
The Tiepoint recloser, unlike the Sectionalizing and Midpoint recloser is normally open.
It closes in response to a loss of all phase voltages from one source if the other source phase
voltages are live. Once closed, the Tiepoint breaker will trip automatically if a downstream
overcurrent condition exists and is not isolated by the midpoint recloser first. The Tiepoint
recloser can be set to employ different fault thresholds depending on which side of the loop
it is supplying, i.e., which side is downstream. After the close operation, it also is set to go
into non-reclose mode for a period of time in the event the fault is between the Midpoint
and Tiepoint. If the control changed to New Settings Group for the close operation, it will
remain in that setting group until the Recloser is opened and the loop scheme is reset.
5.4.4
Operation principle
The Operation setting is used to enable or disable the function. When selected “On” the
function is enabled and respectively “Off” means function is disabled.
The operation of DLCM can be described by using a module diagram (see Figure 179). All
the modules in the diagram are explained in the next sections.
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......