![ABB RER620 Technical Manual Download Page 276](http://html.mh-extra.com/html/abb/rer620/rer620_technical-manual_3180276.webp)
Section 4
1MAC309294-MB F
Protection functions
270
RER620
Technical Manual
Blocking logic
The binary input BLOCK can be used to block the function. The activation of the BLOCK
input deactivates RELEASE output and resets the Timer.
4.5.6.5
Application
The directional negative/zero sequence power protection (32N) function improves the
possibility to obtain selective function of the over-current protection in meshed networks.
The 32N function is used to block or release other over current protection function.
4.5.6.6
Signals
Table 281: 32N input signals
Table 282: 32N measured values
Table 283: 32N output signals
Name
Type
Default
Description
V2
REAL
0.0
Negative sequence voltage
VG
REAL
0.0
Measured residual voltage or Ground voltage
VN
REAL
0.0
Calculated residual voltage or Neutral voltage
I2
REAL
0.0
Negative sequence current
IG
REAL
0.0
Measured residual current or Ground current
IN
REAL
0.0
Calculated residual current or Neutral current
RCA_CTL
BOOL
FALSE
Relay characteristic angle control
BLOCK
BOOL
FALSE
Block signal for all binary outputs
Name
Type
Default
Description
IG_AMPL
REAL
0.0
Measured residual current or Ground current amplitude
IG_ANGL
REAL
0.0
Measured residual current or Ground current phase angle
IN_AMPL
REAL
0.0
Calculated residual current or Neutral current amplitude
IN_ANGL
REAL
0.0
Calculated residual current or Neutral current phase angle
VG_AMPL
REAL
0.0
Measured residual voltage or Ground voltage amplitude
VG_ANGL
REAL
0.0
Measured residual voltage or Ground voltage phase angle
VN_AMPL
REAL
0.0
Calculated residual voltage or Neutral voltage amplitude
VN_ANGL
REAL
0.0
Calculated residual voltage or Neutral voltage phase angle
I2_AMPL
REAL
0.0
Negative sequence current amplitude
I2_ANGL
REAL
0.0
Negative sequence current phase angle
V2_AMPL
REAL
0.0
Negative sequence voltage amplitude
V2_ANGL
REAL
0.0
Negative sequence voltage phase angle
BLOCK
BOOL
FALSE
Block signal for all binary outputs
RCA_CTL
BOOL
FALSE
Relay characteristic angle control
Name
Type
Description
RELEASE
BOOL
Release signal if directionality criteria is satisfied
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......