Section 4
1MAC309294-MB F
Protection functions
220
RER620
Technical Manual
The module calculates the start duration (
START_DUR
) value which indicates the
percentage ratio of the start situation and set operate time (DT). The start duration is
available according to the selected value of the
Operation mode
setting.
Table 235: Start duration value
The combined start duration
START_DUR
indicates the maximum percentage ratio of the
active protection modes. The values are available via the Monitored data view.
Blocking logic
There are three operation modes in the blocking functionality. The operation modes are
controlled by the
BLOCK
input and the global setting “
Configuration/System/
Blocking
mode”
which selects the blocking mode. The
BLOCK
input can be controlled by a binary
input, a horizontal communication input or an internal signal of the relay program. The
influence of the
BLOCK
signal activation is preselected with the global setting
Blocking
mode
.
The
Blocking mode
setting has three blocking methods. In the “Freeze timers” mode, the
operate timer is frozen to the prevailing value. In the “Block all” mode, the whole function
is blocked and the timers are reset. In the “Block OPERATE output” mode, the function
operates normally but the
OPERATE
output is not activated.
4.4.1.5
Application
The frequency protection function uses the positive phase-sequence voltage to measure the
frequency reliably and accurately.
The system frequency stability is one of the main principles in the distribution and
transmission network maintenance. To protect all frequency-sensitive electrical apparatus
in the network, the departure from the allowed band for a safe operation should be
inhibited.
The overfrequency protection is applicable in all situations where high levels of the
fundamental frequency of a power system voltage must be reliably detected. The high
fundamental frequency in a power system indicates an unbalance between production and
Freq> OR df/dt
A parallel operation between the protection methods is enabled. The
START
output is
activated when either of the measured values of the protection module exceeds its set
value. A detailed information from the active module is available at the
STR_OFRQ
and
STR_FRG
outputs. The shortest operate delay time from the set
Operate Tm Freq
or
Operate Tm df/dt
is dominant regarding the
OPERATE
output. The time characteristic is
according to DT. The characteristic that activates the
OPERATE
output can be seen
from the
OPR_OFRQ
or
OPR_FRG
output. If the frequency gradient restores before the
module operates, the reset timer is activated. If the timer reaches the value set by the
Reset delay Tm df/dt
setting, the operate timer resets and the
STR_FRG
output is
deactivated. If the frequency restores before the module operates, the reset timer is
activated. If the timer reaches the value set by the
Reset delay Tm Freq
setting, the
operate timer resets and the
STR_UFRQ
output is deactivated.
Operation mode in use
Available start duration value
Freq<
ST_DUR_UFRQ
Freq>
ST_DUR_OFRQ
df/dt
ST_DUR_FRG
Operation mode
Description
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......