4.3.5
Negative sequence overvoltage protection 47
4.3.5.1
Identification
4.3.5.2
Function block
Figure 97:
Function block
4.3.5.3
Functionality
The negative-sequence overvoltage protection 47 is used to detect negative-sequence
overvoltage conditions. 47 is used for the protection of machines.
The function picks up when the negative-sequence voltage exceeds the set limit. 47
operates with the definite time (DT) characteristics.
The function contains a blocking functionality. It is possible to block function outputs, the
definite timer or the function itself, if desired.
4.3.5.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The corresponding
parameter values are Enable and Disable.
The operation of negative sequence overvoltage protection can be described by using a
module diagram. All the blocks in the diagram are explained in the next sections.
Figure 98:
Functional module diagram. V
2
is used for representing negative phase
sequence voltage.
Level detector
The calculated negative sequence voltage is compared with the set
Pickup value
setting. If
the value exceeds the set
Pickup value
, the level detector enables the timer.
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Negative sequence overvoltage protection
NSPTOV
U2>
47
V
2
BLOCK
Level
detector
TRIP
PICKUP
Blocking
logic
t
Timer
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......