1MAC309294-MB F
Section 4
Protection functions
RER620
179
Technical Manual
4.1.7
Phase discontinuity protection 46PD
4.1.7.1
Identification
4.1.7.2
Function block
Figure 78:
Function block
4.1.7.3
Functionality
The phase discontinuity protection 46PD is used for detecting unbalance situations caused
by broken conductors.
The function picks up and trips when the unbalance current I
2
/I
1
exceeds the set limit. To
prevent faulty operation at least one phase current needs to be above the minimum level.
46PD trips with DT characteristic.
The function contains a blocking functionality. It is possible to block the function output,
timer or the function itself, if desired.
4.1.7.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The corresponding
parameter values are Enable and Disable.
The operation of phase discontinuity protection can be described by using a module
diagram. All the blocks in the diagram are explained in the next sections.
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Phase discontinuity protection
PDNSPTOC
I2/I1>
46PD
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......