395
Serial communiction, IEC
&KDSWHU
'DWDFRPPXQLFDWLRQ
•
Opto/electrical converter for the PC/RTU
•
PC/RTU
(YHQWV
The events created in the terminal available for the IEC 60870-5-103 protocol are based
on the event function blocks EV01 - EV06. These function blocks include the function
type and the information number for each event input, which can be found in the IEC-
document. See also the description of the Event function.
0HDVXUDQGV
The measurands can be included as type 3.1, 3.2, 3.3, 3.4 and type 9 according to the
standard.
)DXOWORFDWLRQ
The fault location is expressed in reactive ohms. In relation to the line length in reactive
ohms, it gives the distance to the fault in percent. The data is available and reported
when the fault locator function is included in the terminal.
&RPPDQGV
The commands defined in the IEC 60870-5-103 protocol are represented in a dedicated
function block. This block has output signals according to the protocol for all available
commands.
)LOHWUDQVIHU
The file transfer functionality is based on the Disturbance recorder function. The analog
and binary signals recorded will be reported to the master. The eight last disturbances,
that are recorded, are available for transfer to the master. A file that has been transferred
and acknowledged by the master can not be transferred again.
The binary signals, that are reported, are those that are connected to the disturbance
function blocks DRP1 - DRP3. These function blocks include the function type and the
information number for each signal. See also the description of the Disturbance report.
The analog channels, that are reported, are the first four current inputs and the first four
voltage inputs.
&DOFXODWLRQV
6HWWLQJVIURPW0,
The parameters for IEC communication are set via the local HMI. Refer to the Techni-
cal reference manual for setting parameters and path in local HMI.
Summary of Contents for REO 517
Page 10: ... RQWHQWV ...
Page 16: ...6 Introduction to the application manual KDSWHU QWURGXFWLRQ ...
Page 64: ...54 Blocking of signals during test KDSWHU RPPRQ IXQFWLRQV ...
Page 88: ...78 Scheme communication logic ZCOM KDSWHU LQH LPSHGDQFH ...
Page 146: ...136 Unbalance protection for capacitor banks TOCC KDSWHU XUUHQW ...
Page 166: ...156 Dead line detection DLD KDSWHU 3RZHU V VWHP VXSHUYLVLRQ ...
Page 378: ...368 Monitoring of DC analog measurements KDSWHU 0RQLWRULQJ ...
Page 384: ...374 Pulse counter logic PC KDSWHU 0HWHULQJ ...
Page 412: ...402 Serial communication modules SCM KDSWHU DWD FRPPXQLFDWLRQ ...
Page 440: ...430 LED indication module KDSWHU DUGZDUH PRGXOHV ...