7.2
Modbus point list
Modbus data points and structures available in RIO600 modules are described here.
Some of the addresses are reserved and unused, that is, data points always return value
“0” when they are read.
There are two alternatives for Modbus addressing. PLC addressing starts from address
1 while regular Modbus addressing starts from 0. For example, in PLC addressing a
holding register address 234 can be referred to either as 4X register 234 or as 40234.
Similarly, regular Modbus addressing at 234 can be referred to either as 4X register
233 or as 40233.
Modbus addresses in the documentation follow regular Modbus
addressing scheme with addresses starting from 0. For PLC based
addressing scheme the regular Modbus data addresses should be
incremented by one.
Modbus point list can be exported from the connectivity package.
7.2.1
SSR1 System status register (1) device health
System status register address provides information about the health status of the
RIO600 system and all individual modules present in its stack. It also provides status
of the UPS power failure and local/remote mode.
Table 126:
SSR1 System status register (1) device health
Reg A
Type
Scale
IEC 61850 name
SA name
Description
Values
0
Bit
LECM Warning
0 = Ok,
1 = Warning
or error
0.01
Bit
LECM Error
0 = Ok,
1 = Warning
or error
0.02
Bit
Module 1 Health
0 = Ok,
1 = Warning
or error
0.03
Bit
Module 2 Health
0 = Ok,
1 = Warning
or error
0.04
Bit
Module 3 Health
0 = Ok,
1 = Warning
or error
0.05
Bit
Module 4 Health
0 = Ok,
1 = Warning
or error
Table continues on next page
Section 7
1MRS757488 H
Modbus TCP communication
184
RIO600
Installation and Commissioning Manual
Summary of Contents for Remote I/O RIO600
Page 1: ... Remote I O RIO600 Installation and Commissioning Manual ...
Page 2: ......
Page 8: ......
Page 14: ...6 ...
Page 18: ...10 ...
Page 64: ...56 ...
Page 280: ...272 ...
Page 306: ...298 ...
Page 310: ...302 ...
Page 311: ...303 ...