2.3.1.6
CTRL.Dxxxxx2 Controllable disconnector (2)
Table 9:
CTRL.Dxxxxx2 Controllable disconnector (2)
IEC 61850 name
SA name
Description
Values
CTRL.DCCILO2
.EnaCls.stVal
ENA_CLOSE
Close enabled
1=Enabled
.EnaOpn.stVal
ENA_OPEN
Open enabled
1=Enabled
.ItlByPss.stVal
ITL_BYPASS
Interlocking bypass
1=Bypassed
CTRL.DCCSWI2
.Pos.stSeld
SELECTED
CB selected
1=Selected
CTRL.DCXSWI2
.BlkCls.stVal
BLK_CLOSE
Close blocked
1=Blocked
.BlkOpn.stVal
BLK_OPEN
Open blocked
1=Blocked
2.3.1.7
CTRL.Exxxxx1 Controllable earth switch (1)
Table 10:
CTRL.Exxxxx1 Controllable earth switch (1)
IEC 61850 name
SA name
Description
Values
CTRL.ESCILO1
.EnaCls.stVal
ENA_CLOSE
Close enabled
1=Enabled
.EnaOpn.stVal
ENA_OPEN
Open enabled
1=Enabled
.ItlByPss.stVal
ITL_BYPASS
Interlocking bypass
1=Bypassed
CTRL.ESCSWI1
.Pos.stSeld
SELECTED
CB selected
1=Selected
CTRL.ESXSWI1
.BlkCls.stVal
BLK_CLOSE
Close blocked
1=Blocked
.BlkOpn.stVal
BLK_OPEN
Open blocked
1=Blocked
2.3.1.8
CTRL.CCRDIF1 Current circuit failure protection
Table 11:
CTRL.CCRDIF1 Current circuit failure protection
IEC 61850 name
SA name
Description
Values
CTRL.CCRDIF1
.Alm.stVal
FAIL
Fail Alarm
1=Alarm
.Op.general
ALARM
Fail Operate
1=Operate
1MRS756880 C
Section 2
DNP3 data mappings
REM615
15
Point List Manual