11.7
Signal outputs
Table 296: Signal output X100: SO1
Description
Value
Rated voltage
250 V AC/DC
Continuous contact carry
5 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit
time constant L/R<40 ms, at 48/110/220 V
DC
1 A/0.25 A/0.15 A
Minimum contact load
100 mA at 24 V AC/DC
Table 297: Signal outputs and IRF output
Description
Value
Rated voltage
250 V AC/DC
Continuous contact carry
5 A
Make and carry for 3.0 s
10 A
Make and carry 0.5 s
15 A
Breaking capacity when the control-circuit
time constant L/R<40 ms, at 48/110/220 V
DC
1 A/0.25 A/0.15 A
Minimum contact load
10 mA at 5 V AC/DC
11.8
Double-pole power output relays with TCS function
Table 298: Double-pole power output relays with TCS function
Description
Value
Rated voltage
250 V AC/DC
Continuous contact carry
8 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit
time constant L/R<40 ms, at 48/110/220 V
DC (two contacts connected in series)
5 A/3 A/1 A
Minimum contact load
100 mA at 24 V AC/DC
Trip-circuit supervision (TCS):
• Control voltage range
20...250 V AC/DC
Table continues on the next page
1MRS758407 C
Technical data
SMU615
Technical Manual
259